I/O channel configuration
Mix of channels configured
as Pulse inputs or Digital Outputs
Equipment (if an external power is required for the HSPC module):
A power supply with an operating rating of 30 VDC, 5 A (maximum).
5 A fuse
External power supply is not energized.
Review and meet wire requirements (wire gauge, length, wire-end ferrules, etc.)
To wire external power supply (refer to
IMPORTANT NOTE. Prevent short circuit. Verify that the external power positive and
negative connections are wired correctly to the HSPC before energizing the power supply.
1.
Insert External Power In (+) wire in J1-5.
!
WARNING – Fire hazard. Make sure to use a 5 A fuse between the power supply positive (+)
terminal and the HSPC module J1-5 terminal. The fuse prevents a fire hazard in the event of a
short circuit.
2.
Insert External Power In (+) wire in J2-5.
3.
Insert External Power GND (-) wire in J3-5.
4.
Insert External Power GND (-) wire in J5-5.
Figure 3-1: HSPC I/O point and external power wiring
Input configuration
(if applicable)
Inputs may be configured with Wetting
Current/Pullup disabled or enabled.
Figure
4-1):
21 08 74 4MN A A | HS P C C ON FIG UR AT IO N G UI DE | 5
Power Mode
configuration