SUN2000-(50KTL, 60KTL, 65KTL)-M0
User Manual
Figure 6-5 Quick Settings screen (advanced user)
● Set the grid code that applies to the country or region where the PV plant is located and the
● Set user parameters based on the current date and time.
● Set Baud rate, Protocol, and Address based on site requirements. Baud rate can be set to
● When multiple SUN2000s communicate with the SmartLogger over RS485, the RS485
Issue 11 (2024-02-02)
NO TE
SUN2000 model.
4800, 9600, or 19200. Protocol can be set to MODBUS RTU, and Address can be set to any
value in the range of 1 to 247.
addresses for all the SUN2000s on each RS485 route must be within the address range set
on the SmartLogger and cannot be duplicate. Otherwise, the communication will fail. In
addition, the baud rates of all the SUN2000s on each RS485 route must be consistent with
the SmartLogger baud rate.
Copyright © Huawei Technologies Co., Ltd.
6 Commissioning