Figure 7-7 Feature parameters (special user)
----End
Parameter List
Parameter
Automatic OFF due
to communication
interrupted
Automatic ON due
to communication
resumed
Communication
interruption
duration (min)
Soft start/boot time
(s)
Issue 11 (2024-02-02)
Description
The standards of certain countries and
regions require that the inverter must
shut down after the communication is
interrupted for a certain time.
If this parameter is set to Enable, the
inverter automatically starts after
communication recovers. If this
parameter is set to Disable, the
inverter needs to be started manually
after communication recovers.
Specifies the duration for determining
communication interruption. Used for
automatic shutdown for protection in
case of communication interruption.
Specifies the duration for the power to
gradually increase when the inverter
starts.
Copyright © Huawei Technologies Co., Ltd.
7 Man-Machine Interactions
Remarks
If Automatic OFF due to
communication interrupted is
set to Enable and the inverter
communication is interrupted for
a specified time (set by
Communication interruption
duration), the inverter will
automatically shut down.
This parameter is displayed when
Automatic OFF due to
communication interrupted is
set to Enable.
N/A