Fig. 8: Permitted mounting position for all ctrlX CORE controls
End clamps
Fasten end clamps of the type SUP-M01-ENDHALTER on both sides of the control.
End clamps ensure a correct fastening of the control connected to them on the support rail and
they are used as lateral end elements.
Always fasten one end clamp of the station before mounting the control. This ensures the following:
It impedes the shifting of the control.
The installation place for the end clamps is secured.
Do not route cables parallel to motor cables or other strong interference sources to avoid the
coupling of interferences.
Observe the bending radii of the cables when routing.
The cabling of the Ethernet wires may not be outside the building.
Use strain reliefs for all cables and place them the closest possible to the connection of the control.
Install the control only horizontally on a support rail attached to a wall.
Keep the maximum possible distance from interference sources.
Provide the following minimum distances for sufficient cooling:
In case of a several line design, the supply air has to be measured under each line and its limit value
may not be exceeded. For information on ambient temperatures, refer to
conditions of the ctrlX CORE" on page