• Maintain the correct clearance and orientation between the vent and air intake terminals. The vent and air intake
terminals must be at the same height and their center lines must be between 12 and 36 inches apart. Both terminals
must be located on the same wall.
• The bottom of the vent and air intake terminals must be at least 12" above the normal snow line. In no case should
they be less than 12" above grade level.
• The bottom of the vent terminal must be at least 7 feet above a public walkway.
• Do not install the vent terminal directly over windows or doors.
• The bottom of the vent terminal must be at least 3 feet above any forced air inlet located within 10 feet.
• A clearance of at least 4 feet horizontally must be maintained between the vent terminal and gas meters, electric
meters, regulators, and relief equipment. Do not install vent terminal over this equipment.
• Do not locate the vent terminal under decks or similar structures.
• Top of vent terminal must be at least 5 feet below eves, soffits, or overhangs. Maximum depth of overhang is 3 ft.
• Vent terminal must be at least 6 feet from an inside corner.
• Under certain conditions, water in the flue gas may condense, and possibly freeze, on objects around the terminal
including on the structure itself. If these objects are subject to damage by flue gas condensate, they should be
moved or protected.
VENT OPTION #
CLASSIFICATION USED IN THIS
MANUAL
ILLUSTRATED IN FIGURE
VENT PIPE STRUCTURE
PENETRATION
AIR INTAKE PIPE STRUCTURE
PENETRATION
VENT PIPE SIZE
AIR INTAKE PIPE SIZE
BWC150
BWC225
BWC150
BWC225
EXHAUST TERMINAL
AIR INTAKE TERMINAL
VENT MATERIAL
AIR INTAKE MATERIAL
"N.R" - Not recommended
"N.A." - Not applicable
TABLE 6.2a: SUMMARY OF HORIZONTAL VENTING OPTIONS
1
HORIZONTAL
DIRECT VENT
6.1
WALL
WALL
3"
4"
55 FT
N.R.
60 FT
N.R.
3" 90 ELBOW
OR TEE
4" 90 ELBOW
APPROVED VENT SYSTEM
SHOWN IN TABLE 6.5
GALVANIZED OR PVC
2
3
(RESERVED
HORIZONTAL
FOR FUTURE
DIRECT VENT
USE)
6.1
WALL
WALL
4"
4"
N.R.
55 FT
N.R.
60 FT
4" 90 ELBOW
OR TEE
4" 90 ELBOW
9
4
5
(RESERVED
(RESERVED
FOR FUTURE
FOR FUTURE
USE)
USE)