9.1 PAC4220 technical data
Measuring inputs for voltage
Input resistance (L N)
Max. power consumption per phase
Measuring inputs for current
Measuring inputs for current
Input current I
I
Measuring range of current
Measuring range for power and energy measurement
Surge withstand capability
Max. permissible continuous current
Max. power consumption per phase
Zero point suppression
Measuring accuracy
Measured variable
Voltage
Current 
Neutral conductor current (calculated)
Apparent power
Active power
Reactive power  
Total apparent power
Total active power
Total reactive power
Total power factor
Line frequency 
Total active energy
Total reactive energy 
THD voltage referred to fundamental
THD current referred to fundamental
2nd ... 64th harmonic of the voltage referred to the fundamental Class 2 (IEC61557-12)
2nd ... 64th harmonic of the current referred to the fundamental Class 2 (IEC61557-12)
102
 
Rated current 1
Rated current 2
Accuracy class
Class 0.2 (IEC 61557-12)
Class 0.2 (IEC 61557-12)
Class 0.2 (IEC 61557-12)
Class 0.5 (IEC 61557-12)
Class 0.2 (IEC 61557-12)
Class 0.5 (IEC 61557-12)
Class 0.5 (IEC 61557-12)
Class 0.2 (IEC 61557-12)
Class 0.5 (IEC 61557-12)
Class 1 (IEC 61557-12)
Class 0.05 (IEC 61557-12)
Class 0.2 (IEC 61557-12)/(IEC 62053-21)
Class 0.5 (IEC 61557-12)/(IEC 62053-23)
Class 2 (IEC61557-12)
Class 2 (IEC61557-12)
1.5 MΩ
150 mW
 
x/1 A
x/5 A
10 ... 120% of rated current
1 ... 120% of rated current
100 A for 1 s
10 A
300 mVA at 5 A
0 ... 10% of rated current
Equipment Manual, L1V30827278B-01