Codes And Standards - Carrier 59TN6C Installation, Start-Up, Operating, Service And Maintenance Instructions

Two-stage, variable-speed, multipoise 35 in. (889 mm) tall, condensing gas furnace
Table of Contents

Advertisement

59TN6C: Installation, Start-up, Operating, Service and Maintenance Instructions
and/or vent to fail prematurely, customer discomfort and/or vent
freezing.
Failure to follow these guidelines is considered faulty installation and/or
misapplication of the furnace; and resulting failure, damage, or repairs
may impact warranty coverage.
For accessory installation details, refer to the applicable instruction
literature.
NOTE: Remove all shipping materials, loose parts bag, and literature
before operating the furnace. See
WARNING
!
FIRE HAZARD
Failure to follow this warning could result in personal injury, death
and/or property damage.
Do not install the furnace on its back or hang furnace with control
compartment facing downward. Safety control operation will be
adversely affected. Never connect return-air ducts to the back of the
furnace. See
Fig.
4.
Table 3 – Loose Parts Bag
DESCRIPTION
Air Intake Pipe Flange
Vent Pipe Flange
Coupling Flange Gaskets
Sharp Tip Screws (Vent and Inlet Flanges)
Vent Pipe Coupling
Vent Pipe Coupling Clamps
Rubber Drain Elbow
Drain Tube Clamps
1/2-in. CPVC to 3/4-in. PVC Pipe Adapter
Gas Line Grommet
Junction Box Cover
Junction Box Base
Green Ground Screw
Blunt Tip Screws (Junction Box)
Thermostat Wire Grommet
Drain Extension Tube (Z-pipe) (Provided separately in
furnace)
WARNING
!
FIRE, INJURY OR DEATH HAZARD
Failure to follow this warning could result in personal injury, death
and/or property damage.
When the furnace is installed in a residential garage, the burners and
burner ignition devices must be located at least 18 in. (457 mm) above
the floor. The furnace must be located or protected to avoid damage by
vehicles. When the furnace is installed in a public garage, airplane
hangar, or other building having a hazardous atmosphere, the furnace
must be installed in accordance with the current edition of NFPA
54/ANSI Z223.1 or CAN/CSA B149.2. See
BACK POSITIONED
DOWNWARD
BACK POSITIONED
UPWARD
Fig. 4 – Prohibited Installations
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Table
3.
QUANTITY
1
1
2
10
1
2
1
4
1
1
1
1
1
3
1
1
Fig.
5.
AIR RETURN
CUT IN BACK
Fig. 5 – Installation in a Garage

CODES AND STANDARDS

Follow all national and local codes and standards in addition to these
instructions. The installation must comply with regulations of the
serving gas supplier, local building, heating, plumbing, and other codes.
In absence of local codes, the installation must comply with the national
codes listed below and all authorities having jurisdiction.
In the United States and Canada, follow all codes and standards for the
following:
Safety
• US: Current edition of National Fuel Gas Code NFPA 54/ANSI
Z223.1 and the Installation Standards, Warm Air Heating and Air
Conditioning Systems ANSI/NFPA 90B
• CANADA: Current edition of National Standard of Canada, Natural
Gas and Propane Installation Code (NSCNGPIC) CAN/CSA B149.1
General Installation
• US: NFPA 54/ANSI Z223.1 and the NFPA 90B. For copies, contact
the National Fire Protection Association Inc., Batterymarch Park,
Quincy, MA 02269; or for only the NFPA 54/ANSI Z223.1 contact the
American Gas Association, 400 N. Capitol, N.W., Washington DC
20001
• CANADA: NSCNGPIC. For a copy, contact Standard Sales, CSA
International, 178 Rexdale Boulevard, Etobicoke (Toronto), Ontario,
M9W 1R3, Canada
Combustion and Ventilation Air
• US: Section 9.3 of the current edition of NFPA54/ANSI Z223.1 Air
for Combustion and Ventilation
• CANADA: Part 8 of the current edition of CAN/CSA B149.1, Venting
Systems and Air Supply for Appliances
Duct Systems
• US and CANADA: Current edition of Air Conditioning Contractors
Association (ACCA) Manual D, Sheet Metal and Air Conditioning
Contractors National Association (SMACNA), or American Society
of
Heating,
Refrigeration,
(ASHRAE) Fundamentals Handbook
Acoustical Lining and Fibrous Glass Duct
• US and CANADA: Current edition of SMACNA, NFPA 90B as tested
by UL Standard 181 for Class I Rigid Air Ducts
Gas Piping and Gas Pipe Pressure Testing
• US: Current edition of NFPA 54/ANSI Z223.1; Chapters 5, 6, 7, and 8
and national plumbing codes.
CANADA: Current edition of CAN/CSA-B149.1, Parts 4, 5, 6, and 9.
In the state of Massachusetts:
• This product must be installed by a licensed plumber or gas fitter.
• When flexible connectors are used, the maximum length shall not
exceed 36 in. (914 mm).
A12182
• When lever type gas shutoffs are used they shall be T-handle type.
6
18-IN. (457.2 mm)
MINIMUM TO BURNERS
and Air
Conditioning
Engineers
A93044

Advertisement

Table of Contents
loading

Table of Contents