P0
DHW thermostat
P1
Solar delay timing This function does not affect the correct functioning of this boiler model.
Pump function-
P2
ing
Relay 1
P3
(optional)
Relay 2
P4
(optional)
Relay 3
P5
(optional)
Description
Establishes the boiler ignition and switch-off mode in DHW mode.
0 - Ignition occurs when the water contained in the storage tank drops
by 7°C with respect to the temperature set and switches off when the
temperature is at -4°C with respect to the value set (solar deactivated)
1 - Ignition occurs when the water contained in the storage tank drops
by 2°C with respect to the temperature set and switches off when the
temperature is at +1°C with respect to the value set (solar deactivated)
2 - Ignition occurs when the water contained in the storage tank drops
by 10°C with respect to the temperature set and switches off when
the temperature is at the value set (Solar activated)
The pump can function in two ways.
0 intermittent: in winter "mode" the circulator is managed by the room
thermostat or by the remote control
1 continuous: in "winter" mode the circulator is always powered and is
therefore always in operation
The boiler is set-up for functioning with the relay P.C.B. (optional),
which can be configured
0 = Off
1 = Main zone control
2 = General alarm
3 = CH phase active
4 = External gas valve power supply
5 = (Do not use on this boiler model)
The boiler is set-up for functioning with the relay P.C.B. (optional),
which can be configured
0 = Off
1 = General alarm
2 = CH phase active
3 = External gas valve power supply
4 = Secondary zone control (from TA on relay P.C.B. contact)
5 = Heat pump
The boiler is set-up for functioning with the relay P.C.B. (optional),
which can be configured
0 = Off
1 = Chiller remote activation
2 = General alarm
3 = CH phase active
4 = External gas valve power supply
5 = heat pump
6 = activation of storage tank pump
Personalized
Range
Default
0
On = -7°C
Off = -4°C
1
On = -2°C
2
Off = +1°C
2
On = -10°C
Off = +0°C
0 - 30 sec-
0
onds
0 - 1
0
0 - 5
1
0 - 5
0
0 - 6
0
value
53