Siemens SENTRON 3WL10 Equipment Manual page 97

Hide thumbs Also See for SENTRON 3WL10:
Table of Contents

Advertisement

Accessories
3.2 Electromechanical accessories
The coils work with a current pulse ≥ 100 ms or with constant power input (100% ON time in
%).
Note
If the opening command was issued with a shunt trip, the circuit breaker can be reclosed with
a closing command after the shunt trip has been switched off followed by a wait time ≥ 30 ms.
The opening command always has priority over the closing signal.
Technical specifications
Rated control supply
voltage U
Operating limits
Switch-on power
Continuous power
Break time ST
Make time CC
Miniature C-characteristic circuit breakers in accordance with VDE0641 with the same current rating
1)
may be used as an alternative to fuses.
96
24 V
30 V
s
48 V
60 V
110 to 120 V
120 to 127 V
220 to 240 V
240 to 250 V
380 to 400 V
415 to 440 V
AC
DC
ST: 70 to 110% U
s
CC: 85 to 110% U
s
300 VA
300 W
3.5 VA
3.5 W
35 ms
50 ms
3VA27 molded case circuit breakers & 3WL10 air circuit breakers
Equipment Manual, 10/2023, L1V30499596002-03
Fuse determined from
characteristic curves
1)
DIAZED fuse (operation‐
al class gL/gG) 10A TDz
(slow)
DIAZED fuse (operation‐
al class gL/gG) 4A TDz
(slow)
DIAZED fuse (operation‐
al class gL/gG) 2A TDz
(slow)
 