Siemens SENTRON 3WL10 Equipment Manual page 196

Hide thumbs Also See for SENTRON 3WL10:
Table of Contents

Advertisement

Alarms of ETUs of the 6-series
The electronic trip units of the 6-series indicate the signals and alarms on the display and with
the warning displays. This LED ACT additionally indicates that the ETU is ready for operation.
Display of the LED ACT
The LED name "ACT" stands for ACTIVE. This LED indicates that the ETU is ready for operation.
If the LED does not light up, the power supply of the ETU is interrupted and the ETU is not
ready to operate.
ACT
Flashing slowly
(1 Hz; 0.1 s on / 0.9 s off)
Off
3VA27 molded case circuit breakers & 3WL10 air circuit breakers
Equipment Manual, 10/2023, L1V30499596002-03
LED ACT
Warning display 1
Warning display 2
"i Test" control key
Display
Alarm / status
ETU ready
ETU without power supply
Operation
6.2 Alarms
Measure / comment
No measures required
Check the power supply of the
ETU via the main circuit or the
auxiliary conductors.
195