Connection and commissioning
5.5 Commissioning
Test
Checks
Protection function
1. Make sure that the circuit breaker is in the CLOSED (ON) position and that the main circuits are not
test
2. Connect the ETU via the TD410 or TD420 test device with a laptop on which the powerservice
3. Run the protection function test with powerservice and check whether all protection functions are
Trip test
1. Make sure that the circuit breaker is in the CLOSED (ON) position and that the main circuits are not
(ETU of the 3-series)
2. Connect the test device TD410, TD420, or TD310 to the ETU.
3. Press the test key of the ETU for at least 9 seconds.
4. Check whether the circuit breaker has tripped or the TU reset button has moved forward.
Trip test
1. Make sure that the circuit breaker is in the CLOSED (ON) position and that the main circuits are not
(ETUs of the 6-series)
2. Connect the ETU via the TD410 or TD420 test device with a laptop on which the powerconfig
3. Perform the trip test with powerconfig
4. Check whether the circuit breaker has tripped or the TU reset button has moved forward.
5.5

Commissioning

You can read how to operate the circuit breaker during each test point in Chapter Operation
(Page 183).
5.5.1

General tests

Electric shock!
Test the circuit breaker only while the switchboards are de-energized.
Note
General testing of the circuit breaker is necessary in the following cases:
• The circuit breaker is put into operation for the first time.
• The circuit breaker is inactive for a long time and during storage under certain ambient
conditions
The tests contain the procedures that must only ever be performed by electrically skilled persons.
Electrically skilled person (IEV 195-04-01): Person with relevant education and experience to
enable him or her to perceive risks and to avoid hazards which electricity can create.
178
carrying any current.
software is installed.
working correctly.
carrying any current.