Air conditioner
Installation manual
ACTNMPEH
• Thank you for purchasing this Samsung air conditioner.
• Before operating this unit, please read this manual carefully and retain it for future
reference.
DB68-09549A-00

Advertisement

loading

Summary of Contents for Samsung AC TNMPEH Series

  • Page 1 Air conditioner Installation manual ACTNMPEH • Thank you for purchasing this Samsung air conditioner. • Before operating this unit, please read this manual carefully and retain it for future reference. DB68-09549A-00...
  • Page 2 Contents Safety Information Installation Procedure Step 1 Checking and preparing accessories Step 2 Choosing the installation location Step 3 Optional: Insulating the body of the indoor unit Step 4 Installing the indoor unit Step 5 Purging inert gas from the indoor unit Step 6 Cutting and flaring the pipes Step 7 Connecting the assembly pipes to the refrigerant pipes Step 8 Performing the gas leak test...
  • Page 3 • This manual explains how to install an indoor unit authorised centres or returned to the retailer so that with a split system with two SAMSUNG units. The use it can be disposed of correctly and safely. of other types of units with different control systems •...
  • Page 4 Safety Information Installing the unit Do not install the air conditioner in following places. • Place where there is mineral oil or arsenic acid. Resin parts flame and the accessories may drop or water WARNING may leak. The capacity of the heat exchanger may reduce or the air conditioner may be out of order.
  • Page 5 section of leads, protections…) are compliant with Install the circuit breaker. the electric specifications and with the instructions • If the circuit breaker is not installed, electric shock or provided in the wiring scheme. Always verify that all fire may occur. connections comply with the standards applicable to Make sure that the condensed water dripping from the the installation of air conditioners.
  • Page 6 Installation Procedure Step 2 Choosing the installation Space requirements for installation location Construction Standard for Inspection Hole 1 In case, the ceiling is tex tile, Inspection hole dose not need. General requirements for installation location 2 In case, the ceiling is plaster board, Inspection hole depends on Inside height of the ceiing.
  • Page 7 Indoor unit dimensions AC018TNMPEH / AC024TNMPEH (Unit: mm) 700(7x100) 22-ø3.2 hole (Air around) 817 (Air outlet duct ange) Inspection hole 900 (Suspension position) Discharge side Suction side Description Name AC018TNMPEH AC024TNMPEH Liquid pipe connection ø6.35(1/4") Gas pipe connection ø12.70(1/2") ø15.88(5/8") Drain pipe connection VP25 (OD32)(without drain pump) Power supply connection...
  • Page 8 Installation Procedure AC036TNMPEH,AC048TNMPEH (Unit: mm) 1100(11x100) 30-ø3.2 hole 1268 (Air outlet duct ange) (Air around) 1300 1350 (Suspension position) Inspection hole 1300 1400 Discharge side Suction side Name Description Liquid pipe connection ø9.52(3/8") Gas pipe connection ø15.88(5/8") Drain pipe connection VP25 (OD32)(without drain pump) Power supply connection Air discharge flange...
  • Page 9 AC060TNMPEH (Unit: mm) 1236 (Suspension position) 1200 18-ø3.2 hole 1000 (Air outlet duct ange) (Air around) 900(6x150) Inspection hole 1200 1300 05 01 02 03 Discharge side Suction side Name Description Liquid pipe connection ø9.52(3/8") Gas pipe connection ø19.05(3/4") Drain pipe connection VP25 (OD32)(without drain pump) Drain pipe connection Using drain pump (Optional)
  • Page 10 Installation Procedure Step 3 Optional: Insulating the body • Insulate the discharge and suction part at the same time when you insulate connection duct. of the indoor unit Step 4 Installing the indoor unit When deciding on the location of the air conditioner with the owner, the following restrictions must be taken into account 1 Place the pattern sheet on the ceiling at the spot where...
  • Page 11 weight of the indoor unit. Before hanging the unit, test When the drain hose is installed to the right. the strength of each attached suspension bolt. • If the length of suspension bolt is more than 1.5m, it is required to prevent vibration. •...
  • Page 12 Installation Procedure and incorrectly. AC060TNMPEH Pipe cutter Liquid 90° 90° refrigerant port Pipe Oblique Rough Burr refrigerant port 3 To prevent any gas from leaking out, remove all burrs at the cut edge of the pipe, using a reamer. 4 Slide a flare nut on to the pipe and modify the flare. R 0.4 to 0.8 mm NOTE •...
  • Page 13 • Tighten the nuts to the specified torques. If CAUTION overtightened, the nuts could be broken so refrigerant may leak. • If the pipes require brazing ensure that OFN (Oxygen Free Nitrogen) is flowing through the system. 2 Be sure to use insulator which is thick enough to cover •...
  • Page 14 Installation Procedure AC060TNMPEH AC018/024/036/048TNMPEH Liquid side Liquid refrigerant port Insulator refrigerant port Gas side Drain hose connection port AC060TNMPEH NOTE • The designs and shape are subject to change according to the model. Step 8 Performing the gas leak test Liquid side To identify potential gas leaks on the indoor unit, inspect the connection area of each refrigerant pipe using a leak...
  • Page 15 Step 9 Insulating the refrigerant pipes • Wind the refrigerant pipe with insulation tape if it is exposed to outside sunlight. Once you have checked that there are no leaks in the • Install the refrigerant pipe respecting that the system, you can insulate the piping and hose.
  • Page 16 Installation Procedure Insulation type (heating/cooling) Standard High humidity Pipe Pipe size Remarks (Less than (Over 30°C, 30°C, 85%) 85%) EPDM, NBR Ø6.35 to Ø9.52 Liquid 3 Wrap the supplied large sealing pad over the metal pipe clamp and drain hose to insulate and fix it with clamps. Ø12.7 to Ø19.05 4 Insulate the complete drain piping inside the building...
  • Page 17 AC018/024/036/048TNMPEH 1~1.5m Hanger Flexible hose Horizontal drainpipe Ceiling more than 1/100 slope With the drain pump 1 The drain pipe should be installed within 300mm to 550mm from the flexible hose and then lift down 20mm or more. 2 Install horizontal drainpipe with a slope of 1/100 or AC060TNMPEH more and fix it by hanger space of 1.0~1.5m.
  • Page 18 Installation Procedure 1 Fix the case at with bolts on the side of the control box Step 13 Connecting the power and in the indoor unit.(See the picture). communication cables 2 Attach the external controller PCB to the case in the control box of the indoor unit.
  • Page 19 1 phase (AC036/048TNMPEH) Indoor power supply Power supply Max/Min(V) Indoor power cable Indoor Unit ±10% 1ø,220 to 240 V,50 Hz 1.5 mm², 3 wires F1 F2 Communication cable 0.75 mm², 2 wires Cable clamp Communication: M3.5 screw AC power: M4 screw Outdoor Unit 1(L) 2(N)
  • Page 20 Installation Procedure Step 14 Optional: Extending the • Method 2: Twist the wire cores together and push it into the sleeve. power cable Method 1 Method 2 1 Prepare a crimping tool and the following tools. Tools Spec Shape Crimping pliers MH-14 Connection sleeve Connection sleeve...
  • Page 21 Step 15 Setting additional functions Method 1 Method 2 of wired remote control Insulation tape IInsulation tape Automatic Air-Volume (The function can't be used at AC060TNMPEH model) Automatic Air-Volume function must be performed for CAUTION each indoor unit with the wired remote control attached. •...
  • Page 22 Installation Procedure button to enter a automatic air-volume setting • If the duct configurations have been changed, screen. automatic air-volume function perform again. 4 Press the button to select 1 to enable automatic air-volume operation. External Static Pressure (ESP) setting for phase 5 Select mode No.
  • Page 23 Data bit Model AC048TNMPEH AC060TNMPEH Static 1 2 3 Main Menu Sub-menu Option Code for Indoor Unit Pressure 01B17C-1C50D0- 01116C-1C54CC- 0≤SP≤3 278C96-370045 27A0AF-370048 01B17C-1C5464- 01116C-1C582F- 3<SP≤5.2 278C96-370045 27A0AF-370048 01B17C-1C5496- 01116C-1C5952- 5.2<SP≤7 278C96-370045 27A0AF-370048 01B17C-1C54C8- 01116C-1C5984- 7<SP≤9 278C96-370045 27A0AF-370048 01B17C-1C581A- 01116C-1C59B7- 9<SP≤12 278C96-370045 27A0AF-370048...
  • Page 24 Installation Procedure Step 16 Setting the indoor unit option code In order to set the indoor unit option code use the wired remote controller and follow the directions below. Data bit 1 2 3 Main Menu Sub-menu 4 Press the button to to exit to normal mode.
  • Page 25 Step 17 Setting indoor unit addresses 1 Press the buttons at the same time for more than 3 seconds and then a Main menu will be and installation options displayed. Set the indoor unit address and installation option with 2 Press the button to select and then press remote controller option.
  • Page 26 Installation Procedure NOTE NOTE • Press the button anytime during setup to exit • The first digit represents the page number and the without setting. remaining five digits are installation option. • Address will not be applied if you don't press •...
  • Page 27 Option No. : 02XXXX-1XXXXX-2XXXXX-3XXXXX Option SEG1 SEG2 SEG3 SEG4 Explanation PAGE MODE Use of external temperature sensor Indication Details Indication Details Indication Details RESERVED Indication Disuse and Details Option SEG5 SEG6 SEG7 SEG8 Explanation Use of central control PAGE Use of drain pump Indication Details Indication Details...
  • Page 28 Installation Procedure Option SEG13 SEG14 SEG15 SEG16 Explanation PAGE Use of external control Setting the output of external control Ionizer Indication Details Indication Details Indication Details Indication Details Disuse On/Off control off control Window on/off control Existing Thermo on Disuse Control Disuse On/Off control...
  • Page 29 5 Press the button to save and complete the option setting. 6 Press the button to exit to normal mode. NOTE • Press button anytime during setup to exit without setting. • Option code will not be applied if you don't press button.
  • Page 30 Installation Procedure – Connect the S-net pro2 to F1 and F2. – Enable the entrance control and set the mode, set temperature, and fan speed. [Master] [Slave] ETO operation specifications 1 Main indoor unit – Based on the external contact control settings, the main indoor unit decides whether to generate output when an error (indoor unit stop) occurs.
  • Page 31 Appendix Troubleshooting • If an error occurs during the operation, one or more LED flickers and the operation is stopped except the LED. • If you re-operate the air conditioner, it operates normally at first, then detect an error again. Indicators Abnormal conditions Remarks...
  • Page 32 Troubleshooting • If an error occurs, is displayed on the wired remote controller. If you would like to see an error code, press the Test button. Error mode Contents Error type Indoor unit communication error Communication error Duplicated address setting error Communication error No response error address from indoor unit Communication error...
  • Page 33 Error mode Contents Error type Compressor V limit error Outdoor unit protection control error DC LINK over/low voltage error Outdoor unit protection control error [Inverter] Compressor rotation error Outdoor unit protection control error [Inverter] Current sensor error Outdoor unit protection control error [Inverter] DC LINK voltage sensor error Outdoor unit protection control error EEPROM Read/Write error...