4.15 Discharge Pipe Temperature Control

F3
Error Code
Method of Error
An error is determined with the temperature detected by the discharge pipe thermistor.
Detection
Error Decision
 If the temperature detected by the discharge pipe thermistor rises above A°C, the
Conditions
 The error is cleared when the discharge pipe temperature has dropped below B°C.
 If the error repeats, the system is shut down.
 Reset condition: Continuous run for about 60 minutes without any other error
 12 class
(1) Above 80 Hz (rising), above 75 Hz (dropping)
(2) 40 ~ 80 Hz (rising), 35 ~ 75 Hz (dropping)
(3) Below 40 Hz (rising), below 35 Hz (dropping)
 18 class
 24 class
(1) Above 50 Hz (rising), above 45 Hz (dropping)
(2) 21 ~ 50 Hz (rising), 16 ~ 45 Hz (dropping)
(3) Below 21 Hz (rising), below 16 Hz (dropping)
Supposed
 Defective discharge pipe thermistor
Causes
 Defective electronic expansion valve or coil
 Refrigerant shortage
 Water mixed in refrigerant
 Defective stop valve
 Defective outdoor unit PCB
Part 6 Service Diagnosis
compressor stops.
80 Hz
40 Hz
A (°C)
B (°C)
116
85
50 Hz
21 Hz
(Defective outdoor heat exchanger thermistor or outdoor temperature thermistor)
A (°C)
116
110
110
Frequency
Zone (1)
Zone (2)
Zone (3)
A (°C)
115
103
95
Frequency
Zone (1)
Zone (2)
Zone (3)
Troubleshooting
B (°C)
104
98
88
75 Hz
35 Hz
B (°C)
85
73
65
45 Hz
16 Hz
(R20778)
R6000880
75