Daikin FTKM-U Series Service Manual page 71

Inverter pair wall mounted type r-32
Table of Contents

Advertisement

SiMX042215E
Troubleshooting
Check the connection wires
between the indoor unit and the
outdoor unit.
Check the voltage of the
connection wires on the indoor
terminal strip between No. 1
and No. 3, and between No. 2
and No. 3.
Check the LED A on the outdoor
unit PCB.
Reference
Check No.11 Refer to P.92
Part 6 Service Diagnosis
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Check the power supply voltage.
Is the
voltage fluctuation
within ±10% from the
rated value?
YES
Is there any wiring error?
NO
Properly insulated?
YES
Is LED A blinking?
Blink
Rotate the
outdoor fan manually.
Does the outdoor fan rotate
smoothly?
YES
Check No.11
Check the power supply
waveform.
Is there any disturbance?
YES
NO
YES
NO
Continuously ON or OFF
NO
NO
Troubleshooting
Correct the power supply.
Correct the connection wires
between the indoor unit and
the outdoor unit.
Replace the connection wires
between the indoor unit and
outdoor unit.
Replace the outdoor unit PCB
(main PCB).
Replace the outdoor fan motor
and the outdoor unit PCB
(main PCB).
Replace the indoor unit PCB
(control PCB).
Locate and eliminate the
cause of the disturbance of
the power supply waveform.
(R24742)