Control system for smoke ventilation
Hide thumbs Also See for KFX 210:

Advertisement

Quick Links

KFX 210/211/212/213/214
KFC 210/220
Instructions for VELUX control
system for smoke ventilation
ENGLISH
VAS 453812-2015-01

Advertisement

Table of Contents
loading

Summary of Contents for Velux KFX 210

  • Page 1 KFX 210/211/212/213/214 KFC 210/220 Instructions for VELUX control system for smoke ventilation ENGLISH VAS 453812-2015-01...
  • Page 2: Table Of Contents

    KFC to another - Ventilation switch - Rain sensor - Receive alarm from a primary, external control system - Transmit alarms or error indications to other external equipment Replacement of frame in control unit Technical data 2 VELUX VELUX ® ®...
  • Page 3: Important Information

    VELUX A/S: ........
  • Page 4: Contents Of Packaging

    Blank lid unit. Break-glass point Frame with instructions KFK 100-104*) Keys, rubber bushes, screws Smoke detector KFA 100*) and cable ties Coloured frame*) Labels *) Is delivered depending on type Back-up batteries of control system. 6 VELUX VELUX ® ®...
  • Page 5: Overview Of Printed Circuit Board

    14-15 Break-glass point FACU terminals 23, 27 Temperature fuse Error indication Status indications 20-22 Motor 2 14-15 Alarm signals 23-24, 27-28 Smoke detector Link Batteries Setting Comfort opening time Rain sensor Rain signal - output 8 VELUX VELUX ® ®...
  • Page 6: Break-Glass Point Kfk 100

    Colour of frame for break-glass point in control unit The white frame can be replaced by the coloured frame supplied (applies to KFX 211, SMOKE 212, 213 and 214 and KFC 210 and 220). See page 30. 10 VELUX VELUX ® ®...
  • Page 7: Rain Sensor Kla 200

    Automatic closing of windows opened for comfort ventilation purposes can also be set. This function is only active if switch 4 is set in position ON (see page 16). Min opening time: 2 minutes Max opening time: 60 minutes 12 VELUX VELUX ® ®...
  • Page 8: Motor Terminals

    * 5 x 2.5 mm 28 m 3 x 4 mm 22 m 3 x 6 mm 33 m MOTOR 1 DET. *) 2x2 conductors in parallel Only one smoke ventilation window CSP per motor terminal 14 VELUX VELUX ® ®...
  • Page 9: Setting Of Switches

    NB: If a rain sensor is fitted, the comfort ventilation The time is set by means of the timer "AUTO CLOSE function will automatically be blocked if rain is detected. TIME", see section Ventilation switch KFK 200. 16 VELUX VELUX ® ®...
  • Page 10: Back-Up Batteries

    Lead cable as shown and fasten it in cable gland. For optimum fixing, the rubber bush can be replaced by one of the rubber bushes supplied. Install battery holder. 18 VELUX VELUX ® ®...
  • Page 11: Status And Error Indication In Control System

    The error is also indicated in the integrated break-glass point and pos- service intervals are also error indicated with a yellow light-emitting sible additional break-glass points. diode in the integrated break-glass point and possible additional break- glass points and an acoustic alarm. 20 VELUX VELUX ® ®...
  • Page 12: Connected Control Units

    ALARM FACU ALARM FACU + – + – Control unit 1 Control unit 2 Control unit 3 22 VELUX VELUX ® ®...
  • Page 13: Receive And Transmit Error Indications From One Control Unit Kfc To Another

    Note: Do not connect the control systems if you would like a local ventilation switch. LINK LINK LINK COMFORT COMFORT Control unit 1 Control unit 2 Control unit 3 Control unit 1 Control unit 2 24 VELUX VELUX ® ®...
  • Page 14: Rain Sensor

    Note: Do not overload the 24 V outlet with other additional connections. Fire Alarm Control Unit RAIN OUT RAIN IN RAIN OUT RAIN IN FACU ERROR SMOKE RAIN + – Control unit 1 Control unit 2 FACU ALARM FACU + – + – 26 VELUX VELUX ® ®...
  • Page 15: Transmit Alarms Or Error Indications To Other External Equipment

    An alarm will be transmitted from the ALARM terminal where a potential-free relay switches in case of alarm. Error indications will be transmitted from the ERROR terminal where a potential-free relay switches in case of alarm. ALARM ERROR – 28 VELUX VELUX ® ®...
  • Page 16: Replacement Of Frame In Control Unit

    − With batteries: 8.0 kg Weight KFC 220: − Without batteries: 3.7 kg − With batteries: 8.6 kg Cabinet colour: RAL 9016, white Maintenance: Once a year or according to local requirements (service timer 15 months) 30 VELUX VELUX ® ®...
  • Page 17 02245/32 3 50 01 848 8775 VELUX Australia Pty. Ltd. VELUX Italia s.p.a. 1300 859 856 045/6173666 VELUX-Japan Ltd. VELUX Bosna i Hercegovina d.o.o. 0570-00-8145 033/626 493, 626 494 VELUX Belgium VELUX Lietuva, UAB (010) 42.09.09 (85) 270 91 01...