Diagnostics – BACnet MS/TP Slave
Select the BACnet MS/TP Slave in the dropdown menu on the Diagnostics Page. Additional diagnostic
information can be found by clicking the Help button.
NOTE: This page will auto-refresh every five seconds with the latest data.
Clear All Values - This will only affect displayed values.
1) This will reset all displayed values back to zero and clear the Status Strings.
2) If viewing BACnet MS/TP Slave, this will only clear the values for the BACnet MS/TP Slave section of
the gateway.
Device Status:
1) Connected – The gateway is connected to a BACnet MS/TP master.
2) Not Connected – The gateway is not connected to a BACnet MS/TP master.
3) Error: Timeout – If the Inactivity Timeout is set to non-zero, the gateway has not received a
read/write request in the amount of time specified by the inactivity timeout.
LED Status:
1) Good Communication (Solid Green) - Connected to a BACnet MS/TP master.
2) Never Connected (Blink Green) – Gateway has never been connected to a BACnet MS/TP master.
3) Connection Timeout (Blink Red) –If the Inactivity Timeout is set to non-zero, the gateway has lost a
connection to the BACnet MS/TP master due to no Read/Write Requests received.
4) Port Not Configured (Solid Red) – Port Configured in the BACnet MS/TP Slave configuration page is
not enabled in the Port Configuration page.
Real Time Automation, Inc.