4) Heartbeat 100ms Update
a) The Heartbeat 100ms Update variable can be used as a heartbeat that updates once every
100ms. The variable starts at 0 on gateway startup and increments by 1 every 100ms. This can
be mapped into a destination on one of the available protocols to monitor the gateways
connection status. If the value stops updating every 100ms the gateway is offline.
5) Heartbeat 1000ms Update
a) The Heartbeat 1000ms Update variable can be used as a heartbeat that updates once every
1000ms. The variable starts at 0 on gateway startup and increments by 1 every 1000ms. This can
be mapped into a destination on one of the available protocols to monitor the gateways
connection status. If the value stops updating every 1000ms the gateway is offline.
6) XY_NetBmpStat
a) If a protocol is a Client/Master, there is a Network Bitmap Status that is provided on the
Diagnostics Info page under the Variables section.
b) Since a Client/Master may be trying to communicate with multiple devices on the network, it
may be beneficial to know if a Server/Slave device is down. By using this Network Bitmap Status,
you can expose the connection statuses of individual devices. Values shown are in HEX.
i)
0x00000002 shows that only device 2 is connected
ii) 0x00000003 shows that only devices 1 and 2 are connected
iii) 0x0000001f shows that all 5 devices are connected (shown in image above)