BACnet MS/TP Subordinate Object Configuration – Binary Objects
Click the Set Up BACnet Names, Units, and COV button at the bottom of the BACnet MS/TP Subordinate
Configuration page to access the Object Configuration page for this device.
When in Auto-Configure Mode, these fields are not configurable. You MUST be in Manual Configure
Mode.
Follow these steps to configure binary inputs or outputs in Manual Configure Mode:
1) Select Binary Input or Binary Output from the upper left dropdown menu.
2) Select a Group to use.
a) These group names are defined on this page under the "Group Name" dropdown menu.
3) Enter a Name to identify this object on the network.
The combination of Group and Name should be unique for each point in the gateway.
Real Time Automation, Inc.
27
1-800-249-1612