[82] Compressor current protection
[108] Transient over current in IPM module rectifier side software
[110] IPM module hardware over current
[123] Transient over current in IPM module rectifier side hardware
Check if voltage of power
Check if wire of electric box
is correct and if compressor
If compressor is normal
(compressor coil resistor
If power module is normal
If there are the other
failure recently, such as
Solve the failures due to
relative information
supply in normal
Yes
wire is fixed well
Yes
insulation)
Yes
Yes
112, 113, 117
Yes
No
Improver power supply circuit
No
Correct the wiring due to diagram
No
Replace compressor
No
Replace power module
No
Remove the failure
59