Indoor Capacity Range; Scope Of The Manual; Accessories; Accessories Supplied With This Unit - Daikin VRV RXYQ72XBYC Series Installation Manual

System air conditioner
Hide thumbs Also See for VRV RXYQ72XBYC Series:
Table of Contents

Advertisement

5 For RXYQ-X units it is also possible to make several commissioning
field settings through a personal computer interface. For this option
999482P3 is required which is a dedicated cable to communicate
with the outdoor unit. The software for the user interface program
can be obtained from your local Daikin sales office.
INFORMATION
Refer to the technical engineering data for the latest option names.

1.3. Indoor capacity range

NOTE
When the VRV outdoor unit is installed with Low-temperature hydrobox in
the system, refer to those installation manuals and Engineering Data Book.
1.3.1.
Connection Ratio
Connection Ratio = Total capacity index of the indoor units / Capac-
ity index of the outdoor units
Min. connection ratio
Type
Types of connected outdoor units
RXYQ-X type
Single outdoor unit
Double outdoor units
50% (*1)
Triple outdoor units
*1. 70% : RXYQ72X type
Max. connection ratio
Types of connected indoor units
When using
When using
Type
only FXDQ,
at least one
FXMQ-T,
FXZQ05 T,
FXAQ,
FXSQ05 T,
FXSQ07-54 T
FXFQ07/09
Single out-
180% *1
door unit
Double
outdoor
200% *1
160% *1
units
Triple out-
130%
door units
Notes: *1. If the operational capacity of indoor units is more than
130%, low airflow operation is enforced in all the indoor
units. This limitation can be abolished through field setting.
*2. When outdoor-air processing units (FXMQ-MF) and
standard indoor units are connected, the total connection
capacity of the outdoor-air processing units (FXMQ-MF)
must not exceed 30% of the capacity index of the outdoor
units. And the connection ratio must not exceed 100%.
1.3.2. Outdoor Unit Combinations
Total capacity of indoor units needs to be within the specified range.
Capacity Range
6 ton
8 ton
10 ton
RXYQ
72XBYC* 96XBYC* 120XBYC* 144XBYC* 168XBYC* 192XBYC* 216XBYC*
Max. Number
of Connectable
12
16
20
Indoor Units
Capacity Range
20 ton
22 ton
24 ton
RXYQ
240XBYC* 264XBYC* 288XBYC* 312XBYC* 336XBYC* 360XBYC* 384XBYC*
Max. Number
of Connectable
41
45
49
Indoor Units
Note: Values inside brackets are based on connection of indoor units
rated at maximum capacity, 200% for single outdoor units, and
160% for double outdoor units.
3
Types of connected air treatment
FXMQ-MF
When using
When
When
other indoor
FXMQ-MF
FXMQ-MF and
unit models
is only
indoor units are
connected
connected
200% *1
160% *1
100%
100% *2
130%
12 ton
14 ton
16 ton
18 ton
25
29
33
37
26 ton
28 ton
30 ton
32 ton
54
58
62
64

1.4. Scope of the manual

This manual describes the procedures for handling, installing and
connecting the VRV RXYQ-X series. This manual has been prepared
to ensure adequate maintenance of the unit, and it will provide help in
case problems occur.
INFORMATION
The installation of the indoor unit(s) is described in the indoor unit
installation manual provided with the indoor unit(s).

2. Accessories

2.1. Accessories supplied with this unit

Confirm the following accessories are included. The storage location
of the accessories is shown in the figure below.
Accessories assy (piping)
NOTE
Do not throw away any of the accessories until installation is complete.
They are needed for installation work.
Name
Clamp (1)
Clamp (2)
Clamp (3)
Quantity
7 pcs.
1 pc.
1 pc.
Shape
(Small)
(Large)
Liquid side
Liquid side
Name
accessory
accessory
pipe (1)
pipe (2)
Quantity
1 pc.
1 pc.
Shape
72-144X
L type
Name
accessory joint
Quantity
1 pc.
Shape
Accessories assy (operation
and installation manual)
Vinyl tube
Manuals, etc.
5 pcs.
1 pc. each
• Operation Manual
• Installation Manual
• REQUEST FOR THE
INDICATION label
(Installation records)
Gas side
Gas side
accessory
accessory
pipe (1)
pipe (2)
1 pc.
1 pc.
168X
72,120X
96X
144,168X
72X
120X
96,144,168X
English

Advertisement

Table of Contents
loading