Selection Of Refrigerant Branch Kits; System Piping (Length) Limitations - Daikin VRV RXYQ72XBYC Series Installation Manual

System air conditioner
Hide thumbs Also See for VRV RXYQ72XBYC Series:
Table of Contents

Advertisement

Size up for equivalent length for outdoor-indoor units over 295 ft. (90 m)
Outdoor unit
Gas pipe
capacity type
3/4 in. (19.1 mm)
RXYQ72X type
→ 7/8 in. (22.2 mm)
7/8 in. (22.2 mm)
RXYQ96X type
→ 1 in. (25.4 mm)
RXYQ120X type
Increase is NOT allowed
RXYQ144X type
1-1/8 in. (28.6 mm)
→ 1-1/4 in. (31.8 mm)
RXYQ168-216X type
RXYQ240X type
Increase is NOT allowed
1-3/8 in. (34.9 mm)
RXYQ264-336X type
→ 1-1/2 in. (38.1 mm)
RXYQ360-384X type Increase is NOT allowed
(a) If size is NOT available, increase is NOT allowed.

7.4. Selection of refrigerant branch kits

For piping example, refer to 7.3. Selection of piping size on page 10.
• When using REFNET joints at the first branch from the outdoor
units, choose from the following table in accordance with the capac-
ity of the outdoor unit (example: REFNET joint a - see 7.3. Selection
of piping size).
Outdoor unit capacity type
RXYQ 72, 96X type
RXYQ 120-216X type
RXYQ 240-384X type
• For REFNET joints other than the first branch (example REFNET
joint b - see 7.3. Selection of piping size), select the proper branch
kit model based on the total capacity of all indoor units connected
after the refrigerant branch.
Indoor unit capacity index
< 72
72 ≤ × < 111
111 ≤ × < 246
≥246
11
Liquid pipe
3/8 in. (9.5 mm)
→ 1/2 in. (12.7 mm)
(a)
1/2 in. (12.7 mm)
→ 5/8 in. (15.9 mm)
(a)
5/8 in. (15.9 mm)
→ 3/4 in. (19.1 mm)
3/4 in. (19.1 mm)
(a)
→ 7/8 in. (22.2 mm)
Maximum 8 branches can be connected to a header.
Kit name
KHRP26A33T9
KHRP26A33TA
KHRP26M72TU9
KHRP26M72TUA
KHRP26M73TU9

7.5. System piping (length) limitations

KHRP26M73TUA
7.5.1.
Make sure to perform the piping installation within the range of the
maximum allowable pipe length, allowable height difference and al-
lowable length after branching as indicated below.
Kit name
Definitions
KHRP26A22T9
Actual piping length: pipe length between outdoor
KHRP26A22TA
Equivalent piping length: pipe length between outdoor
KHRP26A33T9
units. (Assume equivalent piping length of REFNET joint = 1.6 ft.
KHRP26A33TA
(0.5 m) and REFNET header = 3.3 ft. (1 m) (for calculation purposes of
KHRP26M72TU9
equivalent piping length, not for refrigerant charge calculations).)
KHRP26M72TUA
Total piping length: total piping length from the outdoor
KHRP26M73TU9
units.
KHRP26M73TUA
• Concerning REFNET headers, choose from the following table in
accordance with the total capacity of all the indoor units connected
after the REFNET header.
Indoor unit capacity index
< 72
72 ≤ × < 111
111 ≤ × < 230
≥230
INFORMATION
• How to choose an outdoor multi connection piping kit (needed if the
outdoor unit capacity type is 192 or more). Choose from the follow-
ing table in accordance with the number of outdoor units.
Number of outdoor units
2
3
Piping length restrictions
(1) If the system capacity type is > 168, the distance will be
from the first outdoor unit branch to indoor units.
Kit name
KHRP26M22H9/
KHRP26M22HA:
maximum 4 indoor units
or
KHRP26M33H9/
KHRP26M33HA:
maximum 8 indoor units
KHRP26M33H9
KHRP26M33HA
KHRP26M72H9
KHRP26M72HA
KHRP26M73HU9
KHRP26M73HUA
Branch kit name
BHFP22P100U
BHFP22P100UA
BHFP22P151U
BHFP22P151UA
(1)
and indoor units.
(1)
and indoor
to all indoor
(1)
English