1.3. Indoor capacity range

1.3.1.
Connection Ratio
Connection Ratio = Total capacity index of the indoor units / Capac-
ity index of the outdoor units
Min. connection ratio
Type
Types of connected outdoor units
RXLQ-T type
Single outdoor unit
Double outdoor units
Max. connection ratio
Types of connected indoor units
When using
When using
Type
only
at least one
FXDQ,
FXZQ05 T,
FXMQ-T,
FXSQ05 T,
FXAQ,
FXFQ07/09
FXSQ07-54 T
Single
outdoor
180% *1
unit
200% *1
Double
outdoor
160% *1
units
Notes: *1. If the operational capacity of indoor units is more than
130%, low airflow operation is enforced in all the indoor
units.
*2. When outdoor-air processing units (FXMQ-MF) and
standard indoor units are connected, the total connection
capacity of the outdoor-air processing units (FXMQ-MF)
must not exceed 30% of the capacity index of the outdoor
units. And the connection ratio must not exceed 100%.
1.3.2. Outdoor Unit Combinations
Total capacity of indoor units needs to be within the specified range.
Capacity Range
6 ton
8 ton
72TBTJ*
96TBTJ*
120TBTJ* 144TBTJ* 192TBTJ* 240TBTJ*
RXLQ
72TBYD*
96TBYD* 120TBYD* 144TBYD* 192TBYD* 240TBYD*
72TBYC*
96TBYC* 120TBYC* 144TBYC* 192TBYC* 240TBYC*
Max. Number
of Connectable
12
16
Indoor Units
Note: Values inside brackets are based on connection of indoor units
rated at maximum capacity, 200% for single outdoor units, and
160% for double outdoor units.
3
70%
Types of connected air treatment
FXMQ-MF
When
When using
When
FXMQ-MF
other indoor
FXMQ-MF
and indoor
unit models
is only
units
connected
are connected
200% *1
100%
100% *2
160% *1
10 ton
12 ton
16 ton
20 ton
20
25
33
41

1.4. Scope of the manual

This manual describes the procedures for handling, installing and
connecting the VRV Aurora series outdoor units. This manual has
been prepared to ensure adequate maintenance of the unit, and it will
provide help in case problems occur.
INFORMATION
The installation of the indoor unit(s) is described in the indoor unit
installation manual provided with the indoor unit(s).

2. Accessories

2.1. Accessories supplied with this unit

Confirm the following accessories are included. The storage location
of the accessories is shown in the figure below.
Accessories assy (piping)
NOTE
Do not throw away any of the accessories until installation is complete.
They are needed for installation work.
Name
Clamp (1)
Clamp (2)
Clamp (3)
Quantity
7 pcs.
1 pc.
1 pc.
Shape
(Small)
(Large)
Liquid side
Liquid side
Name
accessory
accessory
pipe (1)
pipe (2)
Quantity
1 pc.
1 pc.
Shape
72-120T
L type
Name
accessory joint
Quantity
1 pc.
Shape
Accessories assy (operation
and installation manual)
Vinyl tube
Manuals, etc.
5 pcs.
1 pc. each
• Operation Manual
• Installation Manual
• REQUEST FOR THE
INDICATION label
(Installation records)
Gas side
Gas side
accessory
accessory
pipe (1)
pipe (2)
1 pc.
1 pc.