user's site.
 It is necessary to choose the place where the inlet and outlet air of the indoor unit is even.
 It is necessary to avoid the places where there are other electrical products, power switch plugs and
sockets, kitchen cabinet, bed, sofa and other valuables right under the lines on two sides of the indoor
unit.
Special tools:
Tool Name
Mini
Vacuum
Pump
Filling Device
Leak Detector
Concentration
Detector
Pressure Gauge
Fire Extinguisher
Maintenance
1). Inspections before maintenance.
(1) Inspection of maintenance environment
 There should be no leaked refrigerant in the room before operation.
 It is only allowed to operate in a room which meets the area requirement on the nameplate.
 It is necessary to make the room keep a continuous ventilation state at the time of maintenance.
 The room in the maintenance should be free from fire or welding, smoking, drying oven or any other
goods temperature higher than 370℃ (R290)/548℃ (R32) which easily produces fire.
 During the maintenance, it is necessary to ensure that any person's any mobile phone or any
electronic product with radiation in the room is powered off.
 The maintenance area should be equipped with a drying powder or carbon dioxide fire extinguisher
and that such fire extinguisher can work.
(2) Inspection of maintenance equipment
 
 
 
 
TCL Air Conditioner Service Manual 
It should be an explosion-proof vacuum pump; can ensure certain precision
and its vacuum degree should be lower than 10Pa.
It should be a special explosion-proof filling device; have certain precision and
its filling deviation should be less than 5g.
It should be calibrated regularly; and its annual leak rate should not exceed
10g.
A) The maintenance site should be equipped with a fixed-type combustible
refrigerant concentration detector and connected to a safeguard alarm
system; its error must be not more than 5%.
B) The installation site should be equipped with a portable combustible
refrigerant concentration detector which can realize two-level audible and
visual alarm; its error must be not more than 10%.
C) The concentration detectors should be calibrated regularly.
D) It is necessary to check and confirm the functions before using the
concentration detectors.
A) The pressure gauges should be calibrated regularly.
B) The pressure gauge used for Refrigerant 22 can be used for Refrigerants
R290 and R161; the pressure gauge used for R410A can be used for
Refrigerant 32.
It is necessary to carry fire extinguisher(s) when installing and maintaining an
air conditioner. On the maintenance site, there should be two or more kinds of
dry powder, carbon dioxide and foam fire extinguishers and that such fire
extinguishers should be placed at stipulated positions, with eye-catching
labels and in handy places.