Download Print this page

S+S Regeltechnik THERMASGARD TM43 Operating Instructions, Mounting & Installation page 11

Immersion ⁄ screw-in ⁄ duct temperature measuring transducer, calibratable, with multi-range switching and active output automatic output switching
Hide thumbs Also See for THERMASGARD TM43:

Advertisement

Available languages

Available languages

  • ENGLISH, page 10
G U
THERMASGARD
Measuring ranges [ °C ]
(adjustable)
– 20...+ 150 °C
– 50... + 50 °C
– 20... + 80 °C
– 30... + 60 °C
0... + 40 °C
0... + 50 °C (default)
0...+ 100 °C
0...+ 150 °C
TEMPERATURE RANGES:
When selecting measuring transducer ranges,
it is necessary to ensure that the maximum temperatures
permissible for sensor ⁄ housing are not exceeded !
Ambient temperature for measuring transducers:
– 30 ...+ 70 °C / –22...+158 °F
Apparent ohmic resistance = see load resistance diagram
® 
THERMASGARD
TM 43
THERMASGARD
® 
TM 65
Output
Inserted Length
I variante
(EL) mm = xx
2-wire
4...20 mA
50 mm / 2 in
4...20 mA
100 mm / 4 in
4...20 mA
150 mm / 6 in
200 mm / 8 in
4...20 mA
4...20 mA
250 mm / 10 in
4...20 mA
300 mm / 12 in
4...20 mA
400 mm / 16 in
Output
Inserted Length
(EL) mm = xx
AOS variante
3-wire
0 -10 V / 4...20 mA
50 mm / 2 in
0 -10 V / 4...20 mA
100 mm / 4 in
150 mm / 6 in
0 -10 V / 4...20 mA
0 -10 V / 4...20 mA
200 mm / 8 in
0 -10 V / 4...20 mA
250 mm / 10 in
0 -10 V / 4...20 mA
300 mm / 12 in
0 -10 V / 4...20 mA
400 mm / 16 in
Automatic Output
Patented analogue interface (patent no. DE 10 2015 015 941 B4)
Switching:
Device automatically detects the required output type 0 -10 V or 4...20 mA.
Extra charge:
Other ranges optional
Cable connection with M12 connector according to DIN EN 61076-2-101 on request
®
TM 43 ⁄ TM 65
Measuring ranges [ °F ]
DIP
DIP
DIP
1
2
3
(adjustable)
O N
O N
O N
OFF
O N
O N
– 58...+ 122 °F
O N
OFF
O N
OFF
OFF
O N
– 22...+ 140 °F
O N
O N
OFF
OFF
O N
OFF
O N
OFF
OFF
OFF
OFF
OFF
Basic device with snap-on lid (IP 54), Standard
Basic device with quick-locking screws (IP 67), Premium
Item No.
TM43-I xx
IP 54
1101-7112-0019-900 1101-7112-2019-900
1101-7112-0029-900 1101-7112-2029-900
1101-7112-0039-900 1101-7112-2039-900
1101-7112-0049-900 1101-7112-2049-900
1101-7112-0059-900 1101-7112-2059-900
1101-7112-0069-900 1101-7112-2069-900
Item No.
TM43-A xx
IP 54
1101-711E-0019-900 1101-711E-2019-900
1101-711E-0029-900 1101-711E-2029-900
1101-711E-0039-900 1101-711E-2039-900
1101-711E-0049-900 1101-711E-2049-900
1101-711E-0059-900 1101-711E-2059-900
1101-711E-0069-900 1101-711E-2069-900
– 4...+ 302 °F
– 4...+ 176 °F
32...+ 104 °F
32...+ 122 °F (default)
32...+ 212 °F
32...+ 302 °F
Item No.
TM43-I xx LCD
IP 54
Item No.
TM43-A xx LCD
IP 54
11
Readout in the display
(switchable)
Imperial
SI (default)
Readout in the display
Temperature [°C] → [°F]
The display value depends
on the set unit system (DIP 4).
Item No.
Item No.
TM65-I xx
TM65-I xx LCD
IP 67
IP 67
1101-7122-0019-900 1101-7122-2019-900
1101-7122-0029-900 1101-7122-2029-900
1101-7122-0039-900 1101-7122-2039-900
1101-7122-0049-900 1101-7122-2049-900
1101-7122-0059-900 1101-7122-2059-900
1101-7122-0069-900 1101-7122-2069-900
1101-7122-0089-900 1101-7122-2089-900
Item No.
Item No.
TM65-A xx
TM65-A xx LCD
IP 67
IP 67
1101-712E-0019-900 1101-712E-2019-900
1101-712E-0029-900 1101-712E-2029-900
1101-712E-0039-900 1101-712E-2039-900
1101-712E-0049-900 1101-712E-2049-900
1101-712E-0059-900 1101-712E-2059-900
1101-712E-0069-900 1101-712E-2069-900
1101-712E-0089-900 1101-712E-2089-900
Rev. Data-V20
DIP
4
[°F]
O N
[°C]
OFF

Advertisement

loading

This manual is also suitable for:

Thermasgard tm65