Nature of fault
Insufficient compressing of a
compressor
Locked compressor
Insufficient switches of the 4-
way valve

14. Technical Data

-
Electric current during operation becomes approximately 20% lower than the normal value.
-
The discharge tube of the compressor becomes abnormally hot (normally 70 to 90°C).
-
The difference between high pressure and low pressure becomes almost zero.
-
Electric current reaches a high level abnormally, and the value exceeds the limit of an ammeter.
some cases, a breaker turns off.
-
The compressor is a humming sound.
-
Electric current during operation becomes approximately 80% lower than the normal value.
-
The temperature different between from the discharge tube to the 4-way valve and from suction
to the 4-way valve becomes almost zero.