Outdoor model
Outdoor unit power supply
Indoor units number
Piping total length
Connecting pipe length
Height difference (Indoor ~ Outdoor)
Height difference (Indoor ~ Indoor)
Function
Capacity
Rated (Min.-Max.) *2
Breaker capacity
Power input (Total) *1, *2
Running current (Total) *1, *2
Power factor (Total) *1, *2
Starting current (Total) *1, *2
Coefficient of performance (C.O.P) (Total) *1, *2
Model
Output
Current *1, *2
Refrigeration oil (Model)
Model
Current *1, *2
Dimensions W x H x D
Weight
Air flow (Rated)
Sound level (Rated)
Fan speed (Rated)
Pre-charged refrigerant quantity (R32)
Refrigerant filling capacity (R32)
*1 Measured under rated operating frequency.
*2 When connected with indoor units below.
MSZ-LN18VG2 + MSZ-LN18VG2 + MSZ-LN18VG2 + MSZ-LN18VG2 + MSZ-LN25VG2 + MSZ-LN25VG2
*3 220 and 240 V are only -
*4 At least 2 indoor units must be connected when using indoor unit with capacity lower than 25 class.
NOTE: Test conditions are based on ISO 5151. (Refrigerant piping length (one way): 5 m)
COOLING INDOOR
Dry-bulb temperature 27.0 °C Wet-bulb temperature 19.0 °C
OUTDOOR Dry-bulb temperature 35.0 °C Wet-bulb temperature 24.0 °C
HEATING INDOOR
Dry-bulb temperature 20.0 °C
OUTDOOR Dry-bulb temperature 7.0 °C Wet-bulb temperature
OBH790L
m
m
m
m
kW
A
W
A
%
A
W
A
L
A
mm
kg
3
m
/h
dB(A)
rpm
kg
kg
.
E1
MXZ-6F120VF2
Single phase
220 - 230 - 240V, 50 Hz *3
1 to 6 *4
Max. 80
Max. 25
Refer to 8 REFRIGERANT SYSTEM DIAGRAM.
Refer to 8 REFRIGERANT SYSTEM DIAGRAM.
Cooling
12.0 ( 3.5 - 14.0 )
3,600
15.2 - 14.5 - 13.9
3.33
MVB33FBFMC
14.2
1.10 (FW68CA)
SIC-88FWJ-D888-4
950 x 1,048 x 330
3,780
55
650
6.0 °C
52
Heating
14.0 ( 3.5 - 16.5 )
32
3,310
15.2 - 14.5 - 13.9
99
14.5
4.23
3,300
12.6
0.3
87
4,620
57
770
2.4
2.4