Mitsubishi Electric MXZ-2F33VF4-E1 Service Manual page 117

Table of Contents

Advertisement

MXZ-5F102VF MXZ-5F102VF2
R.V.coil
OFF
Refrigerant flow in heating
ON
Refrigerant flow in cooling
Union
Indoor unit E
Φ9.52
Indoor unit D
Φ9.52
Indoor unit C
Φ9.52
Indoor unit B
Φ9.52
Indoor unit A
Φ12.7
Union
Indoor unit A
Φ6.35
Strainer #100
Indoor unit B
Φ6.35
Strainer #100
Indoor unit C
Φ6.35
Strainer #100
Indoor unit D
Φ6.35
Strainer #100
Indoor unit E
Φ6.35
Strainer #100
MAX REFRIGERANT PIPING LENGTH
Piping length each indoor unit (a, b, c, d, e)
Total piping length (a+b+c+d+e)
Bending point for each unit
Total bending point
*It is irrelevant which unit is higher.
ADDITIONAL REFRIGERANT CHARGE
Outdoor unit
Refrigerant piping length (one way, 5 units total)
precharged
(g)
2,400
Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the
tables below.
When diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.
For further information on Different-diameter pipe, refer to "PARTS CATALOG".
OBH790L
Compressor
High Pressure Switch
Compressor shell
temperature
thermistor RT62
Muffler
4way Valve
Sub
Muffler
Stop Valve
(with service port)
Capillary Tube
Φ
4.0 x Φ 2.8 x 100
LEV A
LEV B
Strainer
LEV C
#100
LEV D
Stop Valve
LEV E
25 m
80 m
25
80
80 m
0
117
Accumulator
Gas Charge Pipe
Outdoor
heat exchanger
temperature
thermistor
RT68
Taper Pipe
DISTRIBUTOR
Strainer
Strainer
#50
#50
Indoor
units
a
Outdoor
b
unit
c
d
Outdoor unit union diameter
For
Liquid
Indoor unit A
Gas
Liquid
Indoor unit B
Gas
Liquid
Indoor unit C
Gas
Liquid
Indoor unit D
Gas
Liquid
Indoor unit E
Gas
Unit: mm
Outdoor
heat exchanger
Ambient
temperature
thermistor
RT65
Defrost
temperature
thermistor
RT61
Max.
Height
difference
15 m
15 m
15 m
e
Unit: mm (inch)
6.35(1/4)
12.7(1/2)
6.35(1/4)
9.52(3/8)
6.35(1/4)
9.52(3/8)
6.35(1/4)
9.52(3/8)
6.35(1/4)
9.52(3/8)