28 Heating
28.3

Function

The desired temperature setpoint and switc
configured as parameters.
The setpoint temperature is configurable in a
and 40.0°C.
Hysteresis ensures that heating control does
marginal temperature changes, rather only w
deviation from the setpoint.
Hysteresis is configurable in a range between 0
The temperature setpoint and the temperatur
temperatures at which heating control turns on a
Turn'on temperature
Temperature setpoint min
Turn'off temperature
Temperature setpoint plu
Example 1
Temperature setpoint
25.0°C
Temperature hysteresis
1.0°C
Turn'on temperature 24.5°C
Turn'off temperature 25.5°C
Example 2
Temperature setpoint
25.0°C
Temperature hysteresis
0.3°C
Turn'on temperature 24.9°C (value rounded
Turn'off temperature 25.2°C (value rounded
The hysteresis setting can be used to optim
system to the local circumstances.
28.4

Show in home view

The operating state of the heating system or s
displayed in Home view in the temperature mod
Pos. Content
Notes
1
Temperature setpoint
Display of temperatu
measured value sca
2
Status of heating
Status display of "
and/or solar heating
When heating is on,
illuminates.
witch hysteresis can be
a range between 10.0°C
s not turn on and off for
when there is a certain
n 0.1°C and 5.0°C.
ture hysteresis yield the
n and off as follows:
minus half of hysteresis
plus half of hysteresis
ded)
ded)
timally adjust the control
or solar heating system is
odule.
ature setpoint on the
cale
"
"
, the LED symbol
28.5
Menu Heating
The configuration menu for hea
heating control is called up with the
following icon:
The following settings are availabl
able:

Menu $

#
• Inactive (heatin
ating control not used)
Heating mode of
• Heating off (he
operation
(heating control used, but turned off)
• Always heat (re
t (regardless of temperature!)
• Auto (automati
atic temperature control)
Temperature
Desired pool temp
mperature in [°C]
setpoint
Temperature
Permissible tolera
lerance range for temperature control in
hysteresis
[°C]
/
! !
#
Basic settings for heating control.
-
6
#
Safety settings for heating control.
INFO
Allocation of a rela
relay switch output
Heating control ca
can only be activated if you have
allocated a relay sw
y switch output to it beforehand in the
menu.
28.5.1
Basic configuration
ion
The menu
is used to configure the basic settings
is
for heating control. This is general
rally done once at the start'up.
The following settings are availabl
able:
Sub.menu /
! !
#
Pool temperature
Temperature
ure input used for measuring pool
input
temperature:
re:
• Inactive (f
(function not used)
• Temp. inp
input 1 [3]
• Temp. inp
input 2 [4]
• Temp. inp
input 3 [5]
Relay output 'Heating' Relay switch
tch output used for activating heating
(None / OUT
UT 1 [26] / OUT 2 [27] / OUT 3 [30] /
OUT 4 [31] /
] / pH+ [22] / pH' [21] / Alarm [25]).
None
Hea
eating control is inactive
Block if solar heating
Yes / no
is active
Yes
Heati
eating is not turned on when solar heating
is active (sola
solar priority).
Blocking by input.
If an input is
t is selected for this function, then the
heating outpu
utput is turned off if the selected input is in
the state indi
indicated.
Frost protection
See
Temperature sensor
Configure typ
ypes and functions of temperature
configuration
sensors.
63