No.
Cable
3
AC output power
cable
4
Tracking system
power cable
5
DC input
power
cable
Issue 16 (2023-12-20)
Type
● If you connect a
ground cable to the
ground point on the
chassis shell, you
are advised to use a
three-core (L1, L2,
and L3) outdoor
cable and M10
OT/DT terminals
(L1, L2, and L3).
● If you connect a
ground cable to the
ground point in the
maintenance
compartment, you
are advised to use a
four-core (L1, L2, L3,
and PE) outdoor
cable, M10 OT/DT
terminals (L1, L2,
and L3), and M8
OT/DT terminals
(PE). You do not
need to separately
prepare a PE cable.
Three-core outdoor
copper cable with
dual-layer protection
Amphe
PV cable that meets
nol
the 1500 V standard
UTX PV
Connec
tors
MC4
EVO2
PV
Connec
tors
Copyright © Huawei Technologies Co., Ltd.
5 Electrical Connections
Conductor
Outer
Cross-
Diameter
Sectional Area
Range
● Copper-core
24–57 mm
cable:
– L1, L2,
L3: 25–95
2
mm
– PE: ≥ 16
2
mm
. For
details,
see
Table
5-6.
● Aluminum
alloy cable
or copper-
clad
aluminum
cable:
– L1, L2,
L3: 35–95
2
mm
– PE: ≥ 16
2
mm
. For
details,
see
Table
5-6.
14–18 mm
2
6 mm
4.5–7.8 mm
2
4–6 mm
(12–
10 AWG)
4.7–6.4 mm
2
4–6 mm
(12–
10 AWG)
Source
Prepare
d by the
custome
r
Prepare
d by the
custome
r
Prepare
d by the
custome
r
Prepare
d by the
custome
r
54