Page 1
Status Indication & Monitoring (SIM) System Control Module (CM) 10-2539 Installation and Operation Instructions Manual P/N 06-358 Rev. No: 0, 06/05...
Page 3
The information contained in this manual is as who are custodians of the Fike SIM System. accurate as possible. This manual is intended to Others such as architects, engineers, sales and be an aid to Fike authorized sales outlets or marketing personnel, etc.
Page 4
FIKE CORPORATION This page intentionally left blank. Page ii Fike SIM SystemCM 06/05 P/N 06-358...
Store configuration in field module ....................18 Decommissioning Procedure / Check-List ..................19 Spare Parts .............................. 20 Specifications ............................21 10.0 Repair and Return Authorization ......................22 Annex A CONTROL Module Menu ........................23 Fike SIM SystemCM Page iii P/N 06-358 06/05...
Page 6
Exhibit 5-20 Found List Menu Navigation ......................15 Exhibit 5-21 Program FM Counter Menu Navigation ..................16 Exhibit 5-22 Current FM Reading Lookup Table ....................17 Exhibit 6-1 Decommissioning Steps ........................19 Exhibit 8-1 Spare Parts List ..........................20 Page iv Fike SIM SystemCM 06/05 P/N 06-358...
DB9 connection to a computer serial port. This connection is provided to support future upgrades to the SIM system – features associated with this network are currently not implemented. Symbol for “ohm”. Unit of resistance. Fike SIM SystemCM Page 1 of 24 P/N 06-358 06/05...
On the Control Module (CM) the customer has the ability to step through POWER CONTROL SENTINEL SENTINEL SUPPLY MODULE FIELD FIELD UNIT MODULE MODULE Exhibit 2-1 SIM System Block Diagram Page 2 of 24 Fike SIM SystemCM 06/05 P/N 06-358...
Control Module (CM). An onboard form “C” relay enable equipment shutdowns and remote notification of system trouble and alarm conditions. Exhibit 3-2 CM Photo Exhibit 3-1 FM Photo Fike SIM SystemCM Page 3 of 24 P/N 06-358 06/05...
(PLC’s), used industrial environments and are handled through the use of specially designed electronic filters. These filters neutralize the unwanted noise and offer a “clean” signal for further processing. Page 4 of 24 Fike SIM SystemCM 06/05 P/N 06-358...
The Control Module (CM) is the overall status indication point for the SIM control system. It provides a single point for retrieving system status as for troubleshooting all SIM modules attached to the Field Bus. Exhibit 4-1 CM Block Diagram Fike SIM SystemCM Page 5 of 24 P/N 06-358...
Note: The relay designations (NO, NC, and C) are shown in the de-energized state with no power applied. When the CM is powered and the module has no trouble or alarm, the interlock relay is energized. Page 6 of 24 Fike SIM SystemCM 06/05 P/N 06-358...
CM in the SIM System Remote Bus. Exhibit 5-2 Remote Bus Exhibit 5-4 Address DIP Switch Exhibit 5-3 Serial Port 24VDC Fike SIM SystemCM Page 9 of 24 P/N 06-358 06/05...
State. In the Alarm State the red Alarm LED is ‘ON’, and the Interlock Exhibit 5-7 Alarm LED Relay is de-energized. The alarm state is non latching. If the alarm is cleared on the FM the CM returns automatically to the Normal state. Page 10 of 24 Fike SIM SystemCM 06/05 P/N 06-358...
Home mode. between the menu options, and the right key is used to select the desired option. 4. The Menu Mode will timeout after 15 seconds if no activity is present. Fike SIM SystemCM Page 11 of 24 P/N 06-358 06/05...
In order to scroll from –H- to any other option, press the left pushbutton until the desired operational mode is displayed, then select that mode by pressing the right pushbutton. Page 12 of 24 Fike SIM SystemCM 06/05 P/N 06-358...
Press both keys to return to top of list Exhibit 5-14 Alarm List Menu Navigation Example List Items: “A01” – Field Module 01 is in alarm state. “A72” – Field Module 72 is in alarm state. Fike SIM SystemCM Page 13 of 24 P/N 06-358 06/05...
Press both keys to return to top of list Exhibit 5-17 Error List Menu Navigation Example List Items: “E05” – Field Module 05 is in error/trouble state. “E34” – Field Module 34 is in error/trouble state. Page 14 of 24 Fike SIM SystemCM 06/05 P/N 06-358...
Exhibit 5-20 Found List Menu Navigation Example List Items: “F23” – Field Module 23 is connected in the field bus. “F88” – Field Module 88 is connected in the field bus. Fike SIM SystemCM Page 15 of 24 P/N 06-358 06/05...
“P48” – Control module requires 48 Field Module to be active at the field bus connection. Note: If less than 48 modules are found connected the Control Module is in TROUBLE state. Page 16 of 24 Fike SIM SystemCM 06/05 P/N 06-358...
MODE 04 (NO Contact, with wire Supervision) 00 – 0F WIRE OPEN 10 – 2D NORMAL 2E – 41 ALARM 42 - FF WIRE SHORT Exhibit 5-22 Current FM Reading Lookup Table Fike SIM SystemCM Page 17 of 24 P/N 06-358 06/05...
Field to “99” and rolls over. Module and resets the device. Before entering the normal operation mode again the Control Module must be powered off. Page 18 of 24 Fike SIM SystemCM 06/05 P/N 06-358...
FIKE CORPORATION DECOMMISSIONING PROCEDURE / CHECK-LIST The following procedure must only be performed by a Fike qualified Service Engineer, who has been assigned to prepare and complete the decommissioning of the above referenced Explosion Protection System. Each step in the listed procedure must be adhered to and completion/acceptance of this form is mandatory. The Service Engineer must check off each of the following steps.
Three (3) Position Wire Terminal Block for Power Input (P3) & Trouble Relay (P4) End of Line Resistor, 140 Ω, 0.5 Watt for Bus (P1 & P2) 02-10876 Exhibit 8-1 Spare Parts List Page 20 of 24 Fike SIM SystemCM 06/05 P/N 06-358...
- E10-0080, E10-0086, or Killark DB-10106 or larger DB series housing approved for Class II, Div. 1 & 2, Groups E,F,G Class Ill NEMA 3R, 4, 4X, 9(E,F,G) For ATEX installations the CM must be located in a non-hazardous atmosphere. Fike SIM SystemCM Page 21 of 24 P/N 06-358 06/05...
FIKE CORPORATION 10.0 REPAIR AND RETURN AUTHORIZATION Any component that is to be returned to Fike A specific statement as the perceived defect or must be approved for return prior to shipment. In component failure will assist in examining the order for the returned component to receive the part(s).
FIKE CORPORATION ANNEX A CONTROL MODULE MENU (next page) Fike SIM SystemCM Page 23 of 24 P/N 06-358 06/05...
Page 30
Main Menu HOME ALARM ERROR FOUND PROGRAMMED CURRENT READING Navigation Display current Operating Mode: FOUND Momentarily press both switches Displays the FM identification number of devices found connected Menu Mode: Left Button (+): scrolls down the file Press and hold both switches for 5 seconds Right Button (-): scrolls up the file Left Button (+): Scroll menu options Pressing both buttons moves to the top of the file...
Page 31
704 South 10 Street P.O. Box 610 Blue Springs, Missouri 64013 U.S.A. (816) 229-3405 Fax: (816) 229-0314 http://www.fike.com...