Fike Cheetah Xi 50 Operating Instructions
Fike Cheetah Xi 50 Operating Instructions

Fike Cheetah Xi 50 Operating Instructions

Commercial protected premises control unit
Hide thumbs Also See for Cheetah Xi 50:

Advertisement

Quick Links

Local, Remote Station (PPU), Central Station (PPU), and Releasing Service
These instructions must be framed and displayed next to the panel in accordance with NFPA 72, National Fire Alarm
Code for Local Fire Alarm System.
The key to open the panel can be found at this location:
____________________________________________
1.0 OPERATING INFORMATION
Normal Standby
1.
Green AC Power LED lit steady.
2.
All audibles off.
System Alarm
1.
Red Alarm LED flashes.
2.
Local panel sounder/piezo emits slow pulse pattern.
3.
Alarm audible(s) on.
4.
Alarm information visible on LCD (liquid crystal display).
5.
DO NOT press the RESET key at this time.
6.
Press the ACKNOWLEDGE key to turn off the local piezo.
Flashing LEDs will illuminate steady after key press.
7.
Press the SILENCE key to turn off the local piezo and
silence active audibles programmed for silence. Yellow
silence LED will illuminate steady after button press.
8.
Press the F1 key to display the source of the event on the
top line of the LCD (liquid crystal display).
9.
Investigate the source of the alarm condition and take
appropriate actions.
10. After correcting the Alarm condition, press the RESET key
to restore the system to normal operation.
System Trouble/Supervisory
1.
Yellow Trouble and/or Supervisory LED flashes.
2.
Local piezo emits steady tone for System Trouble.
3.
Local piezo emits fast pulse pattern for Supervisory events.
4.
Trouble and/or Supervisory audible(s) on.
5.
Trouble and/or Supervisory information visible on LCD
(liquid crystal display).
6.
DO NOT press the RESET key at this time.
7.
Press the ACKNOWLEDGE key to turn off the local piezo.
Flashing LEDs will illuminate steady after key press.
8.
Press the SILENCE key to turn off the local piezo and
silence active audibles programmed for silence. Yellow
silence LED will illuminate steady after button press.
9.
Press the F1 key to display the source of the event on the
top line of the LCD (liquid crystal display).
10. Investigate the source of the Trouble/Supervisory condition
and take appropriate actions.
11. After correcting the Trouble/Supervisory condition, press the
RESET key to restore the system to normal operation.
OPERATING INSTRUCTIONS
Cheetah Xi™ 50 Control System
(P/N 10-071)
Commercial Protected Premises Control Unit
Trouble Condition – Activation of a trouble signal under normal
operation indicates a problem with the system (not an alarm)
that requires immediate attention. Contact your local service
representative. In most trouble conditions, the fire suppression
system continues to provide protection to the building and its
occupants; however, trouble conditions should not be allowed to
remain and should be investigated and remedied as soon as
possible to insure proper system operation.
Memory Fault – If panel experiences memory failure, local
piezo emits a steady tone, onboard trouble relay transfers, and
panel buttons do not respond to user input. Under this condition,
the panel no longer provides protection to the building and its
occupants. Panel is to be replaced immediately.
2.0 HISTORY AND CONTROL BUTTONS
Step Alarm – Steps through the current ALARM events stored
in the panel's Alarm history buffer. Available only if there are
active alarm events present on the system.
Step Super – Steps through the current SUPERVISORY events
stored in the panel's Supervisory history buffer. Available only if
there are active supervisory events present on the system.
Step All - Steps through ALL events stored in the panel's
current event history buffer. Press the F5 key to toggle between
current events and the panel's entire 3,200 event history buffer.
Drill – Manually activates all outputs and notification appliances
circuits assigned for drill operation in the configuration. Press
the RESET key to clear the drill activation. Displays drill
activation on LCD (liquid crystal display).
Acknowledge – Silences the local piezo sounder and changes
all flashing LEDs to steady. All outputs remain active. Creates
an acknowledge event in the panel history buffer.
Silence – Silences the local piezo sounder and all silenceable
circuits.
creates a silence event in the panel history buffer.
Reset – Resets the control panel to normal operation. All active
control functions (relays and NACs) will deactivate. All display
LEDs will illuminate steady until reset is complete. If events are
still present on the system, control functions will immediately
activate.
Enter – Saves and enters the current configuration settings.
Use navigation buttons to change variables at the blinking cursor
position.
Escape – Toggles event display from OFF-NORMAL (events
present) to SYSTEM NORMAL (no events present) to TOP
LEVEL menu.
Function Keys (F1 – F6) – Used to navigate through the control
panel's menu system during system operation, maintenance and
configuration.
Illuminates the Yellow SILENCE LED steady and
P/N 06-650, Rev 1

Advertisement

loading
Need help?

Need help?

Do you have a question about the Cheetah Xi 50 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Fike Cheetah Xi 50

  • Page 1 OPERATING INSTRUCTIONS Cheetah Xi™ 50 Control System (P/N 10-071) Commercial Protected Premises Control Unit Local, Remote Station (PPU), Central Station (PPU), and Releasing Service These instructions must be framed and displayed next to the panel in accordance with NFPA 72, National Fire Alarm Code for Local Fire Alarm System.
  • Page 2 Refer to Fike document 06-369-2, “Cheetah Xi™ 50 Operation Supervisory – Yellow LED that flashes when the panel enters and Maintenance Manual” for maintenance instructions.