Two-stage heat models can be operated with four stages of gas heating when controlled in either zone sensor, Discharge Air Control, or fresh air tempering mode on
1
the Lennox
CORE unit controller (available when using the CS8500 thermostat or when connected to Building Automation Systems using BACnet, LonTalk, or S-Bus
®
protocols).
HIG H ALTITU DE D ERATE
NOTE - Units may be installed at altitudes up to 2000 feet above sea level without any modification.
At altitudes above 2000 feet, units must be derated to match gas manifold pressures shown
in table below.
At altitudes above 4500 feet units must be derated 4% for each 1000 feet above sea level.
NOTE − This is the only permissible derate for these units.
Refer to the Installation Instructions for more detailed information.