Lennox 18M7901 Installation Instructions Manual

Masonry chimney vent adapter

Advertisement

Quick Links

Litho U.S.A.
E2012
Dallas, Texas
INSTALLATION INSTRUCTIONS FOR MASONRY CHIMNEY VENT ADAPTER KIT
(18M7901) USED WITH 80AF1UH, ML180UH, EL280UH and SL280UH UNITS

Shipping and Packing List

Package 1 of 1 contains:
1 − Vent adapter assembly
1 − Template

Application

The masonry chimney vent adapter kit allows venting of
80 percent efficient furnaces into a tile−lined masonry
chimney without the use of a listed metal lining system.
The vent adapter assembly introduces dilution air into the
flue gases, thus lowering the dew point of the gases and
inhibiting the production of condensation.
This vent adapter is designed for use with 80AF1UH,
ML180UH, EL280UH and SL280UH units installed in
upflow air discharge applications. The kit may be used
with furnaces fueled by either natural gas or LP/propane
gas. Refer to table 1 for a complete listing of the furnaces
with which this adapter kit may be used.
This kit has been CSA International certified for use with
80AF1UH,
ML180UH,
furnaces when installed in accordance with these
instructions.
The furnace must be installed in accordance with all
national and local building codes or, in the absence of
local codes, with the National Fuel Gas Code NFPA
54/ANSI Z223.1 (latest edition) and other applicable
codes. In Canada, installation must be in accordance
with the National Canadian Installation Code CAN/CGA
B149.1 OR B149.2 (latest edition) and other applicable
codes.

Installation Checklist

Verify furnace model numbers approved for use
with kit (table 1).
Verify that winter design temperature is appropri-
ate for application of kit (table 1 and figure 1).
Verify condition of chimney.
Measure chimney height and inside area of lined
chimney.
Verify chimney and vent connector size (tables 3,
4 and 5).
03/12
*2P0312*
GAS UNITS
KITS & ACCESSORIES
506774−01
03/2012
Supersedes 03/2011
EL280UH
and
SL280UH
MASONRY CHIMNEY
This vent adapter kit has been designed and tested for
use with 80AF1UH, ML180UH, EL280UH and SL280UH
units installed in masonry chimney vent applications in
accordance with limitations set by NFPA 54 and the
International Mechanical Code. The included vent
tables and guidelines must be followed exactly to
ensure proper vent and unit operation and to
minimize chimney wet time.
Table 1 also lists the minimum allowable winter design
temperatures for each model when used with the vent
adapter. The map in figure 1 provides winter design
temperatures for the contiguous United States. Portions
of this document are reprinted with permission from NFPA
54: National Fuel Gas Code E1999, National Fire
Protection Association, Quincy, MA 02269. This reprinted
material is not the complete and official position of the
National Fire Protection Association on the referenced
subject, which is represented only by the standard in its
entirety.
TABLE 1
Minimum Winter Design Temperatures for Use with
80AF1UH, ML180UH, EL280UH and SL280UH
Furnaces with Vent Adapter Kit in Both Interior and
Exterior Masonry Chimney Applications
Minimum Winter Design Temperature* °F (°C)
Interior Chimney
All Models
All Input Sizes
Exterior Chimney
*Refer to 99% Minimum Winter Design Temperature table
provided in the current edition of the ASHRAE Fundamentals
Handbook.
Install vent adapter kit (page 6).
Connect blocked vent switch wiring (figure 5, page
7).
Test blocked vent switch.
Test for proper draft and check for spillage (page
8).
Place furnace into operation (page 8).
*P506774-01*
VENT ADAPTER
−10° F (−23° C)
+5° F (−15° C)
506774−01

Advertisement

Table of Contents
loading

Summary of Contents for Lennox 18M7901

  • Page 1 VENT ADAPTER Supersedes 03/2011 INSTALLATION INSTRUCTIONS FOR MASONRY CHIMNEY VENT ADAPTER KIT (18M7901) USED WITH 80AF1UH, ML180UH, EL280UH and SL280UH UNITS This vent adapter kit has been designed and tested for Shipping and Packing List use with 80AF1UH, ML180UH, EL280UH and SL280UH...
  • Page 2 99% Winter Design Temperatures for the Contiguous United States −10 −10 −10 This map is a necessarily generalized guide to temperatures in the contiguous Unites States. Temperatures shown for areas such as mountainous regions and large urban centers may not be accurate. The data used to develop this map was taken from the 1993 ASHRAE Fundamentals Handbook (Chapter 24, Table 1: Climate Conditions for the United States.
  • Page 3 The maximum recommended chimney height in all diameter. applications which include the vent adapter is 35 feet The vent sizing tables allow for two 90° turns. For each (10.6m). additional turn, or equivalent, reduce the maximum capacity listed in the venting tables by 10 percent (.90 X Vent connector from the vent adapter to the tile−lined maximum table capacity).
  • Page 4 Type B Double Wall Vent Connector with Interior Tile−Lined Masonry Chimney Serving a Single 80AF1UH, ML180UH, EL280UH or SL280UH Furnace Equipped with Vent Adapter Kit TILE−LINED MASONRY CHIMNEY B VENT VENT ADAPTER ASSEMBLY FURNACE PERMANENTLY SEALED FIREPLACE OPENING FIGURE 2 Type B Double Wall Vent Connector with Interior or Exterior Tile−Lined Masonry Chimney Serving a Single 80AF1UH, ML180UH, EL280UH or SL280UH Furnace Equipped with Vent Adapter Kit and One or More Drafthood−Equipped Appliances...
  • Page 5 TABLE 4 Multiple Appliance for Interior and Exterior Masonry Chimney Type B Double Wall Vent Connectors Serving a Single 80AF1UH, ML180UH, EL280UH or SL280UH Furnace with Masonry Chimney Vent Adapter Kit and One or More Drafthood−Equipped Appliances Type B Double Wall Connector Diameter − (inches) Vent Connector 6 in.
  • Page 6 TABLE 6 Equivalent Area of Masonry Chimney Liners Inside Liner Inside Diameter or Nominal Liner Size Equivalent Area Dimensions Equivalent Diameter (inches X inches) (square inches) (inches) (inches) 12.2 19.6 4 X 8 2−1/2 X 6−1/2 28.3 38.3 42.7 8 X 8 6−3/4 X 6−3/4 50.3 63.6...
  • Page 7 The 7/8" diameter hole for the electrical conduit can 5 − Use three field−provided, self−drilling sheet metal screws to firmly secure the vent adapter assembly to be located in three different locations in the top cap the round collar of the unit flue transition. Drive one depending upon which furnace model that the vent self−drilling screw through the front and one through adapter is being applied.
  • Page 8 Common Venting Using Tile−Lined Masonry Chimney TILE−LINED MASONRY CHIMNEY 1 FOOT MINIMUM B VENT (2 ft. preferred) VENT ADAPTER ASSEMBLY FURNACE OTHER PERMANENTLY APPLIANCE SEALED FIREPLACE OPENING FIGURE 6 8 − When an exterior masonry chimney is being used, blockage, restriction, leakage, corrosion, or other the furnace must be commonly vented with at least deficiencies which could cause an unsafe one other drafthood−equipped gas−fired appliance.