2.6 E8: Outdoor unit address error
Digital display output
Description
Outdoor unit address error.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition
Trigger condition: Outdoor unit address is set more than 3.
Recover condition: Outdoor unit addresses are set from 0 to 3.
Reset method: Manually restart.
Possible causes
Invalid outdoor unit address.
Main PCB damaged.