Trane 4TVH0086FE000AA Service Manual page 111

Commercial air conditioners
Table of Contents

Advertisement

2.15 P1: Discharge pipe high pressure protection
Digital display output
Description
 Discharge pipe high pressure protection. If the system has a 3-phase protector and the 3-phase protector is connected
with the high pressure switch, the system will display P1 protection when initially powered on, and P1 protection will
disappear once the system reaches a steady state.
 All units stop running.
 Error code is only displayed on the unit with the error.
Trigger / recover condition
 Trigger condition: Discharge pressure ≥ 4.4MPa.
 Recover condition: Discharge pressure ≤ 3.2MPa.
 Reset method: Resume automatically.
Possible causes
 Outdoor unit stop valves are closed.
 Pressure sensor/switch not connected properly or has malfunctioned.
 Excess refrigerant.
 System contains air or nitrogen.
 High pressure side blockage.
 Poor condenser heat exchange.
 Main PCB damaged.
Procedure
ODU stop valves are closed
High pressure sensor connection on main
High pressure sensor has short-circuited
P1
No
PCB is loose
1
No
or failed
2
No
Yes
Open the stop valves
Yes
Ensure the sensor is connected properly
Yes
Replace the sensor
110
Flowchart continued on next page ...

Advertisement

Table of Contents
loading

Table of Contents