1 Error Code Table
Table 6-1.1: Error code table
Error
code
1
E2
Communication error between indoor and outdoor units
Outdoor heat exchanger temperature sensor (T3) error or
E4
outdoor ambient temperature sensor (T4) error
E5
Abnormal power supply voltage
Compressor top or discharge pipe temperature sensor (T7C1/2)
E7
error
E8
Outdoor unit address error
xE9
EEPROM mismatch
xF1
DC bus voltage error
Plate heat exchanger cooling refrigerant outlet temperature
F3
sensor (T6B) error
Plate heat exchanger cooling refrigerant inlet temperature
F5
sensor (T6A) error
xF6
Electronic expansion valve connection error
Communication error between main control chip and inverter
xH0
driver chip
xH4
Inverter module protection
H5
P2 protection appears three times in 60 minutes
H6
P4 protection appears three times in 100 minutes
Number of indoor units detected by outdoor unit not same as
H7
number set on main PCB
H8
High pressure sensor error
H9
P9 protection appears ten times in 120 minutes
C7
PL protection appears three times in 100 minutes
P1
Discharge pipe high pressure protection
P2
Suction pipe low pressure protection
xP3
Compressor current protection
P4
Discharge temperature protection
P5
Outdoor heat exchanger temperature protection
P9
Fan module protection
Content
Remarks
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Refer to Note 3
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
Displayed on the unit with the error
73
Manual re-start
required
2
No
No
No
Yes
Yes
Yes
No
No
No
Yes
No
Yes
Yes
Yes
No
No
Yes
Yes
No
No
No
No
No
No
Table continued on next page ...