Helios AIR1-SM DX Installation And Operating Instructions Manual

Control module dx - for air1 change over register dx
Table of Contents

Advertisement

Available languages

Available languages

Quick Links

Helios Ventilatoren
MONTAGE- UND BETRIEBSVORSCHRIFT
INSTALLATION AND OPERATING INSTRUCTIONS
NOTICE DE MONTAGE ET D'ENTRETIEN
Steuermodul DX - für AIR1 Change Over Register DX
Control module DX - for AIR1 Change Over Register DX
Module de commande DX - pour AIR1 Batterie à détente
directe réversible (DX)
AIR1-SM DX
für AIR1 Lüftungsgeräte XC, XH und RH
for AIR1 ventilation units XC, XH and RH
pour les centrales AIR1 XC, XH et RH
DE
EN
FR

Advertisement

Table of Contents
loading

Summary of Contents for Helios AIR1-SM DX

  • Page 1 Control module DX - for AIR1 Change Over Register DX Module de commande DX - pour AIR1 Batterie à détente directe réversible (DX) AIR1-SM DX für AIR1 Lüftungsgeräte XC, XH und RH for AIR1 ventilation units XC, XH and RH...
  • Page 2: Table Of Contents

    DEUTSCH Inhaltsverzeichnis KAPITEL 1 ALLGEMEINE HINWEISE SEITE 2 Wichtige Informationen ............................Seite 2 Warn- und Sicherheitshinweise .......................... Seite 2 Garantieansprüche – Haftungsausschluss ......................Seite 2 Einsatzbereich – Bestimmungsgemäße Verwendung ................... Seite 2 Funktionsbeschreibung ............................Seite 3 Technische Daten ..............................Seite 3 KAPITEL 2 INSTALLATION UND INBETRIEBNAHME  SEITE 3 Allgemeine Montagehinweise ..........................
  • Page 3: Allgemeine Hinweise

    Wenn die nachfolgenden Ausführungen nicht beachtet werden, entfällt die Gewährleistung. Gleiches gilt für Haftungs- ansprüche an den Hersteller. Der Gebrauch von Zubehörteilen, die nicht von Helios empfohlen oder angeboten werden, ist nicht statthaft. Even tuell auftretende Schäden unterliegen nicht der Gewährleistung.
  • Page 4: Funktionsbeschreibung

    Montage- und Betriebsvorschrift Steuermodul AIR1-SM DX Funktionsbeschreibung Das Steuermodul DX dient zur Verbindung der Regelung des im Kap. 1.4 genannten AIR1-Lüftungsgerätes mit der Regelung einer bauseitigen Kälteanlage. Die zur Verfügung stehenden Ein- und Ausgangssignale von und zur Kälte- anlage sowie die Verbindung zwischen dem Steuermodul DX und dem AIR1-Lüftungsgerät sind im Anschlussplan Kap.
  • Page 5: Einlagerung

    Montage- und Betriebsvorschrift Steuermodul AIR1-SM DX Einlagerung Bei Einlagerung über einen längeren Zeitraum sind zur Verhinderung schädlicher Einwirkungen folgende Maßnahmen zu treffen: Schutz durch trockene, luft- und staubdichte Verpackung (Kunststoffbeutel mit Trockenmittel und Feuchtigkeitsindika- toren). Der Lagerort muss erschütterungsfrei, wassergeschützt und frei von übermäßigen Temperaturschwankungen sein.
  • Page 6: Anschluss Und Inbetriebnahme

    Montage- und Betriebsvorschrift Steuermodul AIR1-SM DX Anschluss und Inbetriebnahme 271 Elektrischer Anschluss Lebensgefahr durch elektrischen Stromschlag! GEFAHR Vor allen Wartungs- und Installationsarbeiten oder vor Öffnen des Klemmenkastens ist das Gerät allpolig vom Netz zu trennen! Der elektrische Anschluss darf nur von einer autorisierten Elektrofachkraft entsprechend den nachstehenden Anschlussplänen ausgeführt werden Der Elektroanschluss muss bis zur finalen Montage all-...
  • Page 7: Anschlussplan

    Montage- und Betriebsvorschrift Steuermodul AIR1-SM DX 275 Anschlussplan SS-1353...
  • Page 8: Verdrahtung Change-Over-Register Dx Und Steuermodul Dx

    Montage- und Betriebsvorschrift Steuermodul AIR1-SM DX 276 Verdrahtung Change-Over-Register DX und Steuermodul DX Übersicht der Ein- und Ausgangssignale Klemme Name Signaltyp Notwendigkeit An- Funktion schluss Lüftung aktiv Abhängig vom Steuermo- Immer wenn die Ventilatoren dul der Kälteanlage. in Betrieb sind, liegen 24 V an.
  • Page 9: Konfiguration Der Bauseitigen Kälteanlage

    Montage- und Betriebsvorschrift Steuermodul AIR1-SM DX 279 Konfiguration der bauseitigen Kälteanlage Wenn das Change-Over-Register DX als Kühler verwendet werden soll, Kühlertyp „DX” wählen. - Die Taste „OK” im Menü „Kühlertyp” drücken. Kühler-Type Im Menü „Alle Einstellungen übernehmen” „Ja” wählen, der Controller wird neu gestartet, um die gewünschte Anwen- dung zu starten.
  • Page 10: Mindestgrenzwertabsenkung Und Pi-Einstellungen

    Montage- und Betriebsvorschrift Steuermodul AIR1-SM DX 2711 Mindestgrenzwertabsenkung und PI-Einstellungen Über das Steuermodul DX kann die Regelung des Change-Over-Registers DX durch Absenken der Zulufttemperatur Untergrenze optimiert werden, sofern eine Raum-Temp-Kaskaden- oder Abluft-Temp-Kaskaden Regelung eingesetzt wird. Dies führt zu einem ruhigeren, kontinuierlicheren Betrieb der Kältemaschinen.
  • Page 11 Montage- und Betriebsvorschrift Steuermodul AIR1-SM DX...
  • Page 12 ENGLISH Table of Contents CHAPTER 1 GENERAL INFORMATION  PAGE 2 Important information ............................Page 2 Warning and safety instructions .......................... Page 2 Warranty claims – Exclusion of liability ......................... Page 2 Area of application – Intended use........................Page 2 Functional description ............................
  • Page 13: Chapter 1 General Information

    If the preceding instructions are not observed, all warranty claims shall be excluded. This also applies for liability claims against the manufacturer. The use of accessories, which are not recommended or offered by Helios, is not permitted. Any possible damages are not covered by the warranty.
  • Page 14: Functional Description

    The available input and output signals from and to the cooling system as well as the connection between the AIR1-SM DX control module and the AIR1 ventilation unit can be seen in the wiring diagram chapter 2.7.5.
  • Page 15: Storage

    Installation and Operating Instructions Control module AIR1-SM DX Storage When storing for a prolonged time, the following steps are to be taken to avoid damaging influences: Protection by dry, airtight and dust-proof packaging (plastic bag with desiccant and humidity indicators). The storage place must be waterproof, vibration-free and free of temperature variations.
  • Page 16: Connection And Commissioning

    The control module DX is equipped with a 1A fuse terminal which protects the circuit in the event of a failure. If the AIR1-SM DX control module is to be operated on a residual current circuit breaker, we recommend: RCD type:...
  • Page 17: Wiring Diagram

    Installation and Operating Instructions Control module AIR1-SM DX 275 Wiring diagram SS-1353...
  • Page 18: Wiring Change-Over Register Dx And Control Module Dx

    Installation and Operating Instructions Control module AIR1-SM DX 276 Wiring change-over register DX and control module DX Overview of input and output signals Terminal Name Signal type Connection requirement Function Ventilation active Depends on control 24 V always present when module DX of the cooling fans in operation.
  • Page 19: Configuration Of On-Site Cooling System

    Installation and Operating Instructions Control module AIR1-SM DX 279 Configuration of on-site cooling system If the change-over register DX is to be used as a cooler, select cooler type “DX”. - Press the “OK” button in the “Cooler type” menu.
  • Page 20: Minimum Limit Value Reduction And Pi Settings

    Installation and Operating Instructions Control module AIR1-SM DX 2711 Minimum limit value reduction and PI settings The control module DX can be used to optimise the control of the change-over register DX by lowering the supply air temperature lower limit, provided a room temp. cascade or extract air temp. cascade control is used.This results in the quieter, continuous operation of the cooling systems.
  • Page 21 Installation and Operating Instructions Control module AIR1-SM DX...
  • Page 22 FRANÇAIS Sommaire CHAPITRE 1 INFORMATIONS GÉNÉRALES  PAGE 2 Informations importantes ............................Page 2 Précautions et consignes de sécurité ........................Page 2 Demandes de garantie – Réserves du constructeur ....................Page 2 Domaines d’utilisation – Utilisation conforme ......................Page 2 Description des fonctionnalités ..........................
  • Page 23: Informations Importantes

    Si les consignes figurant dans cette notice ne sont pas correctement respectées, la garantie s’annule. Il en est de même pour toute implication de responsabilité du fabricant. L’utilisation d’accessoires non conseillés ou proposés par Helios n’est pas permise. Les dégâts causés par cette mau- vaise utilisation ne sont pas inclus dans la garantie.
  • Page 24: Description Des Fonctionnalités

    Notice de montage et d’utilisation Module de commande AIR1-SM DX Description des fonctionnalités Le module de commande DX sert à relier la régulation de l’appareil de ventilation AIR1 mentionné au point 1.4 à la régu- lation d’une installation frigorifique installée par le client. Les signaux d’entrée et de sortie disponibles en provenance et à...
  • Page 25: Stockage

    Notice de montage et d’utilisation Module de commande AIR1-SM DX Stockage Pour un stockage de longue durée et pour éviter toute détérioration préjudiciable, il convient de se conformer aux ins- tructions suivantes : Protéger avec un emballage sec, étanche à l’air et à la poussière (sac en matière synthétique contenant des sachets déshydrateurs et un indicateur d’humidité).
  • Page 26: Raccordement Et Mise En Service

    Notice de montage et d’utilisation Module de commande AIR1-SM DX Raccordement et mise en service 271 Raccordement électrique Danger de mort par choc électrique ! DANGER Mettre impérativement l’appareil hors tension avant tous travaux d’entretien, d’installation ou avant l’ouverture du coffret électrique ! Le raccordement électrique doit être effectué par un électricien qualifié selon les schémas de raccordement de cette notice L’alimentation électrique doit être maintenue hors tension jusqu’à...
  • Page 27: Schéma De Raccordement

    Notice de montage et d’utilisation Module de commande AIR1-SM DX 275 Schéma de raccordement SS-1353...
  • Page 28: Câblage Entre La Batterie À Détente Directe Réversible (Dx) Et Le Module De Commande Dx

    Notice de montage et d’utilisation Module de commande AIR1-SM DX 276 Câblage entre la batterie à détente directe réversible (DX) et le module de commande DX Vue d’ensemble des signaux d’entrée et de sortie Borne Type de BesoinsAnschluss Fonction signal Ventilation active Dépendant du module de...
  • Page 29 Notice de montage et d’utilisation Module de commande AIR1-SM DX 279 Configuration de l’installation de refroidissement installée par le client Si la batterie à détente directe réversible (DX) doit être utilisée comme refroidisseur, sélectionner le type de refroidisseur « DX ». - Appuyer sur la touche « OK » dans le menu « type de refroidisseur ».
  • Page 30: Réduction De La Limite Basse Et Réglages Pi

    Notice de montage et d’utilisation Module de commande AIR1-SM DX 2711 Réduction de la limite basse et réglages PI Le module de commande DX permet d’optimiser la régulation de la batterie à détente directe réversible (DX) en abais- sant la limite inférieure de la température de l’air soufflé, dans la mesure où une régulation en cascade de la température ambiante ou de la température de l’air extrait est utilisée.
  • Page 31 Notice de montage et d’utilisation Module de commande AIR1-SM DX...
  • Page 32 HELIOS Ventilatoren GmbH + Co KG · Lupfenstraße 8 · 78056 VS-Schwenningen HELIOS Ventilateurs · Le Carré des Aviateurs · 157 avenue Charles Floquet · 93155 Le Blanc Mesnil Cedex CH HELIOS Ventilatoren AG · Tannstrasse 4 · 8112 Otelfingen GB HELIOS Ventilation Systems Ltd.