INSTRUCTION MANUAL
MULTI-FUNCTION PID CONTROLLER
(color LCD with touch-panel, Modbus/NestBus communication)
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
• This product is for use in general industrial environ-
ments, therefore may not be suitable for applications
which require higher level of safety (e.g. safety or accident
prevention systems) or of reliability (e.g. vehicle control or
combustion control systems).
• For safety, installation and maintenance of this product
must be conducted by qualified personnel.
■ PACKAGE INCLUDES:
Multi-function PID controller .............................................(1)
Resistor module ...................................................................(2)
CJC sensor ...........................................................................(2)
Mounting bracket ................................................................(2)
Connector adapter (with stereo jack type) .........................(1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures. For more details, refer to
the users manual (EM-6337-B) downloadable at M-Sys-
tem's web site: http://www.m-system.co.jp.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
MODEL
POINTS OF CAUTION
■ CONFORMITY WITH EU DIRECTIVES
• This equipment is suitable for Pollution Degree 2, Instal-
lation Category II (transient voltage 2500V) and Meas-
urement Category II (contact output, transient voltage
2500V). Reinforced insulation (signal input or output to
power: 300V) and basic insulation (signal input or output
to contact output: 300V) are maintained. Prior to instal-
lation, check that the insulation class of this unit satisfies
the system requirements.
• Altitude up to 2000 meters.
• Do not share the grounding point of PE (Protective Earth)
of other devices with FG (Functional Ground). Handle as
signal ground.
• The equipment must be installed such that appropriate
clearance and creepage distances are maintained to con-
form to CE requirements. Failure to observe these re-
quirements may invalidate the CE conformance.
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.
• In order to enable the operator to turn off the power in-
put immediately, install a switch or a circuit breaker ac-
cording to the relevant requirements in IEC 60947-2 and
properly indicate it.
• The equipment is intended to be installed in a industrial
environment defined by EN 61000-6-2, EN 61000-6-4.
• Analog signals may have some fluctuation within ±5 %
during following tests.
EN 61000-4-3
Radiated, radio-frequency, electromagnetic field
EN 61000-4-6
Immunity to conducted disturbances, induced by radio-
frequency fields
EN 61000-4-8
Power frequency magnetic field
■ POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
100 – 240V AC rating: 85 – 264V, 50/60 Hz,
≤ 25VA at 100V AC
≤ 40VA at 240V AC
24V DC rating: 24V ±10%, ≤ 650mA
• Supplying any level of power other than specified above
can damage the unit or the power source.
• Power supply start-up characteristics must reach within
5 seconds to the operational voltage range of the unit.
• Power cables and signal I/O cables for the unit must be
located separately.
• Power cables and signal I/O cables for the unit should not
be bundled together.
• To increase noise resistance of the power input wires,
twist the strands before connecting.
SC200
EM-6338-A Rev.9 P. 1 / 8