MINI-TOP ELECTRONIC ACTUATOR
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
■ PACKAGE INCLUDES:
Mini-Top ..............................................................................(1)
2.5 mm Hexagon key wrench (with option /S) ...................(1)
The Mini-Top is not provided with a yoke or other compo-
nents required for mounting it to a valve. They are to be
provided by the user.
■ MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
POINTS OF CAUTION
■ CONFORMITY WITH EU DIRECTIVES
• This equipment is suitable for Pollution Degree 2 and
Measurement Category II (Full-open/-closed signal, tran-
sient voltage 1500V). Reinforced insulation (Full-open/-
closed signal to other, power or metallic housing: 125V) is
maintained. Prior to installation, check that the insula-
tion class of this unit satisfies the system requirements.
• Altitude up to 2000 meters.
• The equipment must be installed such that appropriate
clearance and creepage distances are maintained to con-
form to CE requirements. Failure to observe these re-
quirements may invalidate the CE conformance.
• Install lightning surge protectors for those wires connect-
ed to remote location. Refer to "LIGHTNING SURGE
PROTECTION" section below.
■ POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
100 – 120V AC rating: 90 – 132V, 47 – 66 Hz, approx. 25VA
200 – 240V AC rating: 180 – 264V, 47 – 66 Hz, approx. 25VA
24V DC: 24V rating ±10%, approx. 0.6A
• A fuse of the following rating is incorporated: 250V/1A
time delay.
• A rush current 1.5 times as high as the above ratings can
flow at the startup.
■ GENERAL PRECAUTIONS
• Remove the power supply to the actuator before wiring to it.
■ INSTALLATION
• Indoor, or outdoor where the MSP is NOT exposed to di-
rect sunlight
• Ambient temperature: -5 to +55°C (23 to 131°F)
• Operating humidity 30 to 85% RH (non-condensing)
• Vibration: 0.5 G (4.9 m/s
2
• Install the MSP where you can reach for maintenance.
Observe at the minimum of 15 centimeters (6 inches)
above the cover.
(linear type)
) max.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
MODEL
■ OUTDOOR USE
• When installing the MSP outdoor or where it is exposed
to rain or water drops, be sure to fasten the cable connec-
tor tightly and leave a slack of the cable.
• Do not mount the MSP in such direction that the output
stem or cable connector is at the top of the MSP unit.
Cable Connector
■ ELECTRICAL CONNECTION
• With DC power type unit, power supply and signal lines
are not isolated. Use an isolator if needed.
• When you use a cable other than the standard 1-meter
cable equipped with non-terminal box type unit and its
extension distance is longer than that, use shielded ca-
bles for signal line, or install signal cables in a separate
piping from power supply cables.
■ LIGHTNING SURGE PROTECTION
• In order to protect the unit from lightning surges entering
through cables, use of appropriate lightning surge protec-
tors are recommended. For 24V DC power supply line,
choose a surge protector with its maximum surge volt-
age 40V or less between lines. Recommended M-System
model: MDP-D24.
■ PID CONTROLLER
• Choose PID parameters carefully so that the MV remains
as stable as possible. Unstable operations shorten the life
of actuator and valve.
■ O-RING, GASKET
• When replacing the actuator cover after adjustments,
check that the O-ring is securely placed in the groove.
• When replacing the terminal box cover, check that the
gasket is in place.
■ YOKE DESIGN
• When a foreign object is caught in the valve, a thrust 2
times greater than the maximum rating could be gener-
ated. Leave enough strength for mechanical components
such like the yoke and stem.
• If the MSP is used on a steam line in temperature con-
trol, it is possible that the MSP's temperature rises high-
er than the ambient temperature due to transmission or
radiation via the steam piping, even when the ambient
temperature is within allowable range.
Use a longer yoke to increase heat dissipation and apply
insulating material.
■ AND ....
• DO NOT loosen the screw fixing the potentiometer stem.
Loosening it could cause a malfunction.
• DO NOT step onto the actuator. DO NOT rest a heavy
object on or against it.
MSP4/MSP5
/MSP6
DO NOT Pull Tightly
EM-4854 Rev.13 P. 1 / 7

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MSP4 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for M-system MSP4 Series

  • Page 1 • When installing the MSP outdoor or where it is exposed to rain or water drops, be sure to fasten the cable connec- Thank you for choosing M-System. Before use, please check tor tightly and leave a slack of the cable.
  • Page 2: Protective Functions

    The protection is reset automatically with applying oppo- placed, there may be problems with the control PCB or the site-direction input signal or turning power off and restart- motor. Contact M-System or sales representative. ing. A foreign object caught in the valve, inappropriate adjust- ■...
  • Page 3 MAX. STROKE MSP4-1 MSP4-2 Drive shaft MSP5-1 MSP5-3 MSP6-3 MSP6-4 Note: The manual operation function is not available for 24V DC power model. EM-4854 Rev.13 P. 3 / 7 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 4: Installation

    • Other Terminal Box Type Applicable wire size 1.25 mm Remove insulation by 10 mm. 3.2 min. 4.5 max. 5.9 max. 3.2 min. EM-4854 Rev.13 P. 4 / 7 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 5: Adjustment Procedure

    Other adjustments which are paint locked are for factory fully go down position (valve stem fully retracted) or ad- use only and should be changed only by qualified M-System just the connecting section of the valve stem. personnel. M-System is not liable for any malfunction or...
  • Page 6: Maintenance

    Re-tighten them. Check that the nut at the valve stem is not loose. Re-tighten it and calibrate. For repair or parts replacement, contact M-System or representatives. ■ LUBRICATION There is no need of oiling the MSP in normal operating conditions.
  • Page 7: Troubleshooting

    Overload cause by a foreign object caught in Check the valve. the valve. ---- Regardless of LED state. For repair or parts replacement, contact M-System or representatives. LIGHTNING SURGE PROTECTION M-System offers a series of lightning surge protectors for protection against induced lightning surges. Please contact M-System to choose appropriate models.