Page 1
INSTALLATION INSTRUCTIONS Package Gas Electric Featuring Industry Standard R-410A Refrigerant RKKN-B073 (6 TON) SERIES ACCREDITED ISO 9001:2008 92-23577-157-00 (BASED ON 92-23577-141-03)
TABLE OF CONTENTS I. Table of Contents ....................2 II. Introduction ......................3 III. Checking Product Received ..................3 IV. Specifications......................3 A. General ......................3 B. Major Components....................3 C. R-410A Refrigerant ...................3 1. Specifications of R-410A................3 2. Quick Reference Guide for R-410A ..............4 3. Evaporator Coil/TXV ..................4 4.
Recognize this symbol as an indi- cation of Important Safety II. INTRODUCTION This booklet contains the installation and operating instructions for your combination gas Information! heating/electric cooling unit. There are some precautions that should be taken to derive maximum satisfaction from it. Improper installation can result in unsatisfactory operation or dangerous conditions.
lines, or be allowed to accumulate in storage tanks. Leak checking should never be done with a mixture of R-410A and air. Leak checking can be performed safely with nitrogen or a mixture of R-410A and nitrogen. 2. Quick Reference Guide For R-410A •...
VII. INSTALLATION WARNING NEvER TEST FOR GAS LEAKS wITh AN OPEN FLAmE. USE A A. GENERAL Install this unit in accordance with The American National Standard Z223.1-latest edition COmmERCIALLy AvAILABLE booklet entitled “National Fuel Gas Code,” and the requirements or codes of the local SOAP SOLUTION mAdE SPECIFI- utility or other authority having jurisdiction.
FIGURE 6 WARNING OUTSIdE SLAB INSTALLATION. CLOSET dISTRIBUTION SySTEm. SLAB FLOOR CONSTRUCTION. ThIS UNIT mAy BE USEd TO hEAT ThE BUILdING OR STRUCTURE dURING CONSTRUCTION IF ThE FOLLOwING INSTALLATION REqUIREmENTS ARE mET. INSTALLATION mUST COmPLy wITh ALL INSTALLATION INSTRUCTIONS INCLUdING: •...
C. ATTACHING EXHAUST AND COMBUSTION AIR INLET HOODS ImPORTANT: do not operate this unit without the exhaust/combustion air inlet hood properly installed. This hood is shipped in a carton in the blower compartment inside the unit and must be attached when the unit is installed. See Figure 3. To attach exhaust/combustion air inlet hood: 1.
FIGURE 7 COvER GASKET dETAIL FOR UNITS ShIPPEd FOR dOwNFLOw APPLICATION BEING CONvERTEd TO hORIzONTAL I631 FIGURE 8 CLEARANCES Recommended Location Clearance A - Front B - Condenser Coil 36“ 12(* C - Duct Side D - Evaporator End VERTICAL E - Above 60“...
WARNING dO NOT, UNdER ANy CIRCUmSTANCES, CONNECT RETURN dUCTwORK TO ANy OThER hEAT PROdUCING dEvICE SUCh AS FIREPLACE INSERT, STOvE, ETC. UNAUThORIzEd USE OF SUCh dEvICES mAy RESULT IN FIRE, CARBON mONOxIdE POISONING, ExPLOSION, PERSONAL INjURy, PROP- ERTy dAmAGE OR dEATh. FIGURE 9 FLAT ROOFTOP INSTALLATION, ATTIC OR dROP CEILING dISTRIBUTING SySTEm.
Page 12
FIGURE 10 LIFTING dETAIL SPREADER BAR LIFTING BEAM CABLE OR CHAIN 5/8( SHACKLE (EACH CORNER) CORNER wEIGhTS By PERCENTAGE I296 FIGURE 11 FIGURE 12 ROOFCURB ROOFCURB ROOFTOP UNIT UNIT ROOFTOP UNI GASKET COUNTER FLASHING* HOLD GASKET NAILER STRIP COUNTER FLA DOWN BRACKET NAILER STRIP...
VIII.GAS SUPPLY, CONDENSATE DRAIN AND VIII.PIPING A. GAS CONNECTION ImPORTANT: Connect this unit only to gas supplied by a commercial utility. 1. Install gas piping in accordance with local codes and regulations of the local utility company. In the absence of local codes, the installation must conform to the specifi- cations of the National Fuel Gas Code, ANSI Z223.1 - latest edition.
In making gas connections, avoid strains as they may cause noise and damage the con- trols. Use a backup wrench on the valve to avoid damage. The capacities of gas pipe of different diameters and lengths in cu. ft. per hr. with pres- sure drop of 0.3 in.
FIGURE 15 FIGURE 14 MANIFOLD PIPE D. ADJUSTING OR CHECKING FURNACE INPUT – Natural Gas Line Pressure 5( - 10.5( w.C. – LP Gas Line Pressure 11( - 13( w.C. – Natural Gas manifold Pressure 3.5( w.C – LP Gas manifold Pressure - 10( w.C. Supply and manifold pressure taps are located on the gas valve body 1/8( N.P.T.
Page 16
TABLE 3 FIGURE 16 CONdENSATE dRAIN METER TIME IN MINUTES AND SECONDS FOR NORMAL INPUT RATING OF FURNACES EQUIPPED FOR NATURAL OR LP GAS METER HEATING VALUE OF GAS BTU PER CU. FT. INPUT SIZE 1000 1040 1100 2500 BTU/HR CU.
FIGURE 18 RECOMMENDED BRANCH CIRCUIT DISCONNECT LOCATION TABLE 5 BRANCh CIRCUIT COPPER wIRE SIzE (Based on 1% voltage drop)* 45 50 BRANCh CIRCUIT AmPACITy SUPPLy wIRE LENGTh-FEET GAS SUPPLY *Taken from National Electric Code ST-1224 E. CONDENSATE DRAIN The condensate drain connection of the evaporator is threaded 3/4( nominal P.V.C. pipe.
Page 18
FIGURE 19 EXAMPLE FOR CONNECTING THRU-BASE POWER AND FIGURE 20 CONTROL WIRING. ALL TyPICAL ThERmOSTAT wIRING CONNECTIONS TO USE WATER-TIGHT FITTINGS. MAINTAIN CLEARANCE WITH ALL COPPER TUBING. FOR INTERNAL WIRING SEE WIRING LABEL ATTACHED TO UNIT. CHASSIS GROUND LOW VOLTAGE WIRE LEADS HIGH VOLTAGE THERMOSTAT...
TABLE 7 FIELd wIRE SIzE FOR 24 vOLT ThERmOSTAT CIRCUITS SOLId COPPER wIRE - AwG. Length of Run – Feet (1) (1) The total wire length is the distance from the furnace to the thermo- stat and back to the furnace. NOTE: DO NOT USE CONTROL WIRING SMALLER THAN NO.
X. FURNACE SECTION CONTROLS AND IGNITION SYSTEM NORMAL FURNACE OPERATING SEQUENCE This unit is equipped with an integrated direct spark ignition control. 1. The thermostat calls for heat. 2. The control board will run a self check to verify that the limit control and manual reset overtemperature control are closed and that the pressure switch is open.
5. Remove control door/access panel. 6. Move switch to the “OFF” position. 7. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! • Do not try to light any appliance. •...
LIMIT CONTROL The supply air high temperature limit cut-off is set at the factory and cannot be adjusted. It is calibrated to prevent the air temperature leaving the furnace from exceeding the maximum outlet air temperature. WARNING dO NOT jUmPER ThIS dEvICE! dOING SO CAN CAUSE A FIRE OR ExPLOSION RESULTING IN PROPERTy dAmAGE, PERSONAL INjURy OR dEATh.
9. Remove the screws (3) connecting the divider plate to the heat exchanger center panel. 10. Remove the turbulators from inside the heat exchangers by inserting the blade of a screwdriver under the locking tabs. Pop the tabs out of the expanded grooves of the heat exchanger.
Cleaning Evaporator Coil 1. The coil should be cleaned when it is dry. If the coil is coated with dirt or lint, vacuum it with a soft brush attachment. Be careful not to bend the coil fins. 2. If the coil is coated with oil or grease, clean it with a mild detergent-and-water solu- tion.
Page 25
XII. GENERAL DATA - RKKN MODELS NOMINAL SIZES 6 TON [21.1 kW] i r e Cooling Performance Continued -> i l o y t i ] 5 . ] 5 . ] 5 . ] 5 . 11.0/NA 11.0/NA 11.0/NA 11.0 Nominal CFM/AHRI Rated CFM [L/s] 2400/2100 [1133/991]...
GENERAL DATA - RKKN MODELS NOMINAL SIZES 6 TON [21.1 kW] i r e Cooling Performance Continued -> i l o y t i ] 5 . ] 5 . ] 5 . ] 5 . 11.0/NA 11.0/NA 11.0/NA 11.0 Nominal CFM/AHRI Rated CFM [L/s] 2400/2100 [1133/991] 2400/2100 [1133/991]...
Page 27
GENERAL DATA - RKKN MODELS NOMINAL SIZES 6 TON [21.1 kW] i r e Cooling Performance Continued -> i l o y t i ] 5 . ] 5 . ] 5 . ] 5 . 11.0/NA 11.0/NA 11.0/NA 11.0 Nominal CFM/AHRI Rated CFM [L/s] 2400/2100 [1133/991] 2400/2100 [1133/991]...
Page 34
COOLING TROUBLEShOOTING ChART wARNING DISCONNECT ALL POWER TO UNIT BEFORE SERVICING. CONTACTOR MAy BREAK ONLy ONE SIDE. FAILURE TO SHUT OFF POWER CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURy OR DEATH. SymPTOm POSSIBLE CAUSE REmEdy Unit will not run •...
Page 35
FURNACE TROUBLEShOOTING GUIdE (COMBINATION HEATING AND COOLING UNITS WITH DIRECT SPARK IGNITION) wARNING hAzARdOUS vOLTAGE dISCONNECT POwER BEFORE LINE vOLTAGE SERvICING. CONNECTIONS SERvICE mUST BE By A TRAINEd, qUALIFIEd SERvICE TEChNICIAN. START SET ThERmOSTAT TO CALL FOR hEAT SET FAN SwITCh TO AUTO •...
NOTE: IF ThE SySTEm GOES INTO LOCKOUT, wAIT 30 SECONdS ANd RESET ThE SySTEm. REPLACE SENSOR mAIN BURNER FLAmE SUSTAINEd • ChECK FLAmE SENSOR POSITION ANd CONdITION • CLEAN FLAmE SENSOR wITh STEEL wOOL • ChECK FLAmE SENSOR wIRES ANd CONNECTIONS REPLACE IGNITION CONTROL •...
Need help?
Do you have a question about the RKKN-B073 Series and is the answer not in the manual?
Questions and answers