Fastsense Plus Specification - Halma Ampac FastSense PLUS Installation & Operation Manual

High sensitivity detector
Table of Contents

Advertisement

16

FastSense PLUS specification

SELV rating
Supply Voltage
Size (mm)
Weight
Operating temperature range
Operating humidity range
Sensitivity range (%Obs/m)
Maximum sensitivity resolution
Detection principle
Particle sensitivity range
Current consumption
Relay Contact Rating
Maximum sampling pipe length
Sampling pipe inlets
Sampling pipe internal diameter
Alarm levels
Bargraph sensitivity range
Bargraph segments
Chamber service intervals
Dust separator replacement intervals
Laser lifetime (MTTF)
Programming Data bus cable
Data bus length
IP rating
IMPORTANT NOTE This equipment is only to be used in accordance with this
specification. Failure to operate the equipment as specified may cause damage to the unit.
Class III or AS/NZS3260:93
21.6V - 26.4V DC
PSU Type: conforming to
AS4428 part 5 or NZ4512
427W x 372H x 95D
5.2kg (Detector) 5.3kg (Command
Module Detector) 6.2kg (Stand-alone
Command Module) 10.1kg (Stand-alone
Command Module + batteries)
-10 to +60°C
0 - 90% Non Condensing
Min = 25% Max = 0.03% FSD
0.0015% Obs/m
Laser light scattering mass detection
0.0003µm to 10µm
400mA (Detector) 450mA (Stand-alone
Command Module) 850mA (Command
Module Detector)
500mA @3 0VDC
200 metres total
4
15-25mm
4 (Fire 2, Fire 1, Pre-Alarm and Aux)
0.0015 - 25% obs/m
26
Greater than 8 years (depending on
environment)
Greater than 5 years (depending on
environment)
Greater than 1000 years
Front panel or PC via RS232/RS485
RS485 data cable
1.2 km IN, 1.2km OUT
IP50
Page 74