One-hour operation
If this button is pressed when operation is stopped,
operation will begin and then stop after 1 hour.
{f pressed when it is operating, will stop after one
hour.
Full power operation
Immediately begins cooling or heating at maximum
power and air flow. Full power stops after 1 hour.
(During heating)
Operates at setting of 32°C.
(During cooling)
Operates at setting of 18°C.
Preheat
When heating is stopped, supplies a small amount
of power to the compressor to make heating start
more quickly.
Preheat does not operate for 2 hours after heating
is stopped. After that, it goes on for 165 minutes
and then stops for 15 minutes, repeatedly.
Atleast | 165
[15
120 min | min
jmin
Sod
eh del ea
Air conditioner OFF
Power ON start
lfa STON wire is inserted into the place indicated
[power ONjon the indoor control board, and the
24
(1) It is ON during operation, and when operation is
(2)
(3
stopped, goes OFF after a delay of 150 seconds
(not immediately).
The minimum OFF time of the relay is 30 seconds.
Air conditioner
ON
operation
OFF
Compressor
oN
relay
| OFF
ri
150 sec.
it will not go ON again before 30 seconds elapses.
lf air conditioner operation is turned on again during
ON
Air conditioner
ON
operation
OFF
ON
ON
LJ OFF
Compressor
relay
150 sec. 30 sec.
the 150 second delay before the compressor relay
goes off, the compressor relay will stay on.
Air conditioner
_ON
ON
operation
OFF
ON
|
Compressor
OOOO
relay
150 sec.