Table Of Contents; Technical Data, Maintenance - D+H RZN 4402-K V2 Instructions For Use Manual

Smoke vent system
Hide thumbs Also See for RZN 4402-K V2:
Table of Contents

Advertisement

Content
Guarantee ................................................. 1
Technical Data, Maintenance ................... 2
Introduction ................................................ 3
System overview ....................................... 4
Mounting of housing .............................. 5-6
Wiring plan ................................................ 9
Connection cable .................................... 10
Connection ......................................... 11-17
Starting .................................................... 18
Encode of line and group ....................... 19
Examination ............................................ 20
Technical Data
Control panel type : RZN 4402/04-K/KS V2
Rated voltage
Rated capacity
Interfering
emission
Res. to jamming
Protective category : II / I
Fire resistance
Protective system : IP30 / IP54
Class of rating
- Monitoring
- Emergency state/
ventilation
Output voltage
Safe output
- rated current
VdS approval No
D+H Highspeed (HS) drives will be
supported.
2/20
RZN 4402/04-K V2 Rev.:1.0
: 230VAC, 50Hz
: 60VA /120VA
: EN 50081-2
EN 55022
: EN 50082-1
EN 61000-4-2 to -6
EN 50204
: -5 to +40 °C
: Continuous duty
: Short-time duty
: 24VDC /
res. ripple <10%
: 2A / 4A
: G 501002
Maintenance
Once a year by a specialist company, who is
authorized by the appliance manufacturer.
Renew test badge, keep control book.
The respective current D+H maintenance
instruction is decisive.
D+H authorized expert companies have
been specially trained by D+H for carrying
out expertly this maintenance, and they get
automatically the latest maintenance
instructions.
Following tests must be carried out in the
course of maintenance:
- Outside examination / inspection of
system components
- Measuring of insulation resistances
- Checking of all relevant power supply units
- Functional testing of connected system
components
- Record of competent carrying-out of
maintenance, and designation according
to directions
Information
An overdue maintenance of the system will
be indicated by the control panel after about
ca. 14 to 16 months. The yellow diode in the
smoke vent button RT 43-H will start flashing.
A malfunction in the smoke vent system will
be continually indicated by the extinguished
green control diodes in the smoke vent
buttons.
After the maintenance time is expired (ca.
14 to 16 months), the ventilation function
OPEN can be interrupted depending on the
presetting of the service timer. Reset can be
carried out by a specialist company only, who
has been authorized by the appliance
manufacturer.
Notes
While an alert, a possible group disturbance
will not notified. Only after reset the alarm, a
fault message will be output.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rzn 4404-k v2Rzn 4402-ks v2Rzn 4404-ks v2

Table of Contents