Control system
Yes
if during fan operation,
if during fan operation,
fan 0Hz order
fan 0Hz order
Yes
No
pag. 73
Confi rmation of defrost
conditions
Fan 0 Hz order, Changeover
of 4 way valve
Capacity control hold
10 sec count
Water side HE inlet
refrigerant temp ≤ 0ºC ?
No
Water side HE inlet
refrigerant temp ≤2ºC ?
No
Capacity control hold
3 min from defrost? start?
Yes
Water side HE inlet
refrigerant temp ≤10ºC ?
Fan operation control?
High pressure ≥2.1MPa ?
Yes
Fan operation start
SMGB0003 rev.0-01/2007
Yes
Load-down output
(10sec output)
Yes
Load-up
continuous output
Yes
High pressure ≥2.4MPa ?
Yes
6 min from defrost? start?
Confi rmation of defrost
fi nish conditions
4 4
No
No