Troubleshooting
Alarm code
[Alarm Stop Reason]
Thermistor for detection of water
side heat exchanger outlet
(backside=inside of heat exchanger)
temperature indicates abnormal
value.
Is Printed Circuit Board for
Relay (PCB
) connector
D
CN3 correctly connected?
Yes
Disconnect connector and
measure resistance. Is the
resistance correct?
Yes
NOTE:
The connector position differs from product model.
Product Model
RCUE 40 ~ 80 AG2
RHUE 40 ~ 80AG2
RCUE 80 ~ 400 AG2
RHUE 80 ~ 240 AG2
pag. 129
SMGB0003 rev.0 - 01/2007
Abnormality of Outlet Water Temperature
No
No
Abnormal
Thermistor
Code
Outlet water temperature Thermistor
(backside of cooler)
Outlet water temperature Thermistor
(backside of cooler)
Outlet water temperature Thermistor
(backside of cooler)
Outlet water temperature Thermistor
(backside of cooler)
Outlet water temperature Thermistor
(backside of cooler)
Outlet water temperature Thermistor
(backside of cooler)
Thermistor for Protection
[PCB Monitoring Position]
No. 1 Cycle: PCBD1 (I/O PCB) CN23Te2
No. 2 Cycle: PCBD2 (I/O PCB) CN23Te2
No. 3 Cycle: PCBD3 (I/O PCB) CN23Te2
No. 4 Cycle: PCBD4 (I/O PCB) CN23Te2
No. 5 Cycle: PCBD5 (I/O PCB) CN23Te2
Plug, Wiring Repair
Replace Thermistor
Replace printed circuit
board for Relay (PCB
)
D
PCB
Connector
PCB
D1
PCB
D1
PCB
D2
CN23
PCB
D3
PCB
D4
PCB
D5
5
5