Structure And Start-Up Method Of Compressor Structure And Start-Up Method Of Compressor - Hitachi RCUE40AG2 Service Manual

Air cooled water chillers, cooling only and heat pump, cooling capacity 106/112 kw - 585/556/1030 kw
Table of Contents

Advertisement

Maintenance
6.7.2. Structure and Start-up method of Compressor
Structure of Compressor
The structure of compressor used in this series is shown below fi gures:
1. A screw of half-sealed compressor is composed with male rotors and female rotors which have 5~6
dies.
2. Capacity is controlled by bypassing the refrigerant moving the slide valve(#7), a part of casing, to a
shaft direction by a hydraulic piston(#9).
The standard specifi cation of motor(#4), built-in the casing, is 200W
Structure drawing of
40ASP-H, 40ASP-Z:
Suction
pag. 163
Discharge
SMGB0003 rev.0 - 11/2006
and start-up.
Name
Main casing
Screw rotor
Roller bearing
Motor
Motor casing
Ball bearing
Slide valve
Rod
Piston
D casing
E cover
Terminal
Gas strainer
C cover
Material
FC250
6 6
FC250
FC250
SM400B
SM400B