Maintenance Criteria Of Screw Compressor - Hitachi RCUE40AG2 Service Manual

Air cooled water chillers, cooling only and heat pump, cooling capacity 106/112 kw - 585/556/1030 kw
Table of Contents

Advertisement

Maintenance

6.2. Maintenance criteria of Screw Compressor

6.2. Maintenance criteria of Screw Compressor

6.2. Maintenance criteria of Screw Compressor
Classifi cation
Time and year
Daily check
Every day
Every 6,000 hrs
Every one year
24,000 hrs
Periodically check
Every 5 years
40,000 hrs
Every 5 years
Remarks
Take the shorter period
Item
1
High pressure switch
2
Refrigerant oil
3
Suction gas strainer, oil strainer.
4
Bearing
5
Rotor
6
thrust liner
7
Set of tooth lock washer (tighten the nuts)
8
Set of P.K.O ring
9
Set of Tefl on ring
NOTE:
: part change
This table is applied in case that operation condition is good and operation record is fully equipped.
Perform compressor check according to the compressor service manual and technical notice.
pag. 152
SMGB0003 rev.0 - 11/2006
Model
air-cooled
water-cooled
Year/month to change or check (min)
Time
1 month
Operation test of safety device and protection device
Check of lubricant oil and change it
Decomposition of compressor
: part change if abnormality is detected in the check
Performance items
Save of operation situation
(pressure, temperature, voltage, current value,
remarks etc.)
remarks etc.)
Operation check of safety device, protection device
Overhaul check of compressor and parts check
Lubricant oil
According to purpose or conditions of use, work
items shall be added individually.
items shall be added individually.
40.000 hr
3.000 hr
6.000 hr
(24.000 hr)
(24.000 hr)
6 month
1 year
5 year
(3 year)
Remark
( ) is for air-cooled.
Change them at the same
time as bearing