Troubleshooting
Example of code indication (alternately
Item
Refrigerant liquid
Refrigerant liquid
Outlet water temp
(backside of heat
exchanger of water
side)
Fan control state
Fan control state
The following operation makes change from alarm data indication mode to normal mode.
1. Press [▲] (SW3) [▼] (SW4) more than 3 sec.
2. In case that un-input state continues 30 seconds.
The following operation makes change from alarm data indication mode to alarm occurrence data mode.
1. Press [▼] (SW4) more than 3 sec.
Electron expansion valve opening indication
By pressing [Ο] (PSW1) on PCB for electron expansion valve more than 3 seconds, actual expansion valve
order opening (pulse) is indicated on the segment. (it is possible during stop / operation)
Once pulses are displayed, pushing again PSW1 enables you to check each cycles expansion valve
position.
PWB
(VD PCB)
G
* Light off by pressing [Ο] more than 3 seconds.
pag. 107
SMGB0003 rev.0 - 01/2007
fl icker)
Segment for check
Check switch
Contents
Outlet water temp (backside of heat exchanger of
water side) [ºC]
-In case of No. 1 outlet water temp is 7ºC
-In case of No. 2 outlet water temp is 7ºC
Indication of electron expansion valve opening
-In case of No. 1 opening is 242 pulse.
-In case of No. 2 opening is 240 pulse.
Press it more
than 3 sec.
PULSES
10 (Thermo OFF)
112 (Min. running value)
656 (Max. running value)
5
5
Flicker
alternately
OPENING %
1,5 %
17%
100%