5.10

Combustion head adjustment

The air damper servomotor 4)(Fig. 5), beyond varying the air out-
put according to the output demand, through a leverage varies
the combustion head adjustment.
This system allows an optimum adjustment also at minimum fir-
ing rate. Similarly to servomotor rotation, it is possible to vary the
opening of the combustion head moving the tie-rod on the holes
(5-6-7-8-10)(Fig. 16).
The selection of the hole to be used is determined based on the
maximum output requested, as illustrated in Tab. F.
In the factory, the adjustment is adjusted for the maximum stroke
(hole 10, Fig. 16).
Leverage hole
5
5
8
8
5
5
6
10
Installation
Output (kW)
From
A
1200
3750
3750
6700
6700
8600
8600
10600
1500
5500
5500
7500
7500
9600
9600
11500
Tab. F
5
6
7
8
10
D11335
19
GB
Fig. 16
20040160