Maintenance

7.1

Notes on safety for the maintenance

The periodic maintenance is essential for the good operation,
safety, yield and duration of the burner.
It allows you to reduce consumption and polluting emissions and
to keep the product in a reliable state over time.
The maintenance interventions and the calibration
of the burner must only be carried out by qualified,
authorised personnel, in accordance with the con-
DANGER
tents of this manual and in compliance with the
standards and regulations of current laws.
Before carrying out any maintenance, cleaning or checking oper-
ations:
7.2

Maintenance programme

7.2.1

Maintenance frequency

The gas combustion system should be checked at
least once a year by a representative of the man-
ufacturer or another specialised technician.
7.2.2

Checking and cleaning

The operator must use the required equipment
during maintenance.
Combustion
Carry out an analysis of the combustion discharge gases.
Significant differences with respect to the previous check indicate
the points where more care should be exercised during mainte-
nance.
Combustion head
Open the burner and make sure that all components of the
combustion head are in good condition, not deformed by the
high temperatures, free of impurities from the surroundings
and correctly positioned.
Electrical current to UV cell (Fig. 42)
Clean the glass cover from any dust that may have accumulated.
To remove the photocell, pull out outwards; it is only pressed in.
Min value for a good work: 70 µA.
If the value is lower, it could be due to:
exhausted photocell
low voltage (lower than 187 V)
bad regulation of the burner
In order to measure the current, use a microammeter of 100 mµA
d.c., connected in series to the photocell, as in the scheme, with
a capacitor of 100 mµF - 1V d.c. at the same level of the instru-
ment.
Maintenance
Disconnect the electrical supply from the burner
by means of the main system switch.
DANGER
Close the fuel interception tap.
DANGER
Wait for the components in contact with heat
sources to cool down completely.
D1143
Burner
Check that there is no abnormal wear or loosen screws, especial-
ly on cams 3)(Fig. 35).
Clean the outside of the burner.
Clean and grease the adjustable profile of the cams.
Fan
Check to make sure that no dust has accumulated inside the fan
or on its blades, as this condition will cause a reduction in the air
flow rate and provoke polluting combustion.
Boiler
Clean the boiler as indicated in its accompanying instructions in
order to maintain all the original combustion characteristics in-
tact, especially the flue gas temperature and combustion cham-
ber pressure.
Pump
The delivery pressure must comply with the table on pag. 18.
The depression must be less than 0.45 bar.
Unusual noise must not be evident during pump operation.
If the pressure is found to be unstable or if the pump runs noisily,
the flexible hose must be detached from the line filter and the fuel
must be sucked from a tank located near the burner.
This measure permits the cause of the anomaly to be traced to
either the suction piping or the pump.
If the problem lies in the suction line, check the filter is clean and
that air is not entering the piping.
Filters (Fig. 43)
Check the filtering baskets on line 1) and at nozzle 2) present in
the system.
Clean or replace if necessary.
37
GB
LIGHT OIL OPERATION
Fig. 42
20040160